Sanken S06-4A005-B Instruction Manual page 147

High performance vector control multifunction inverter
Table of Contents

Advertisement

F5003
Motor frequency rating
F5004
Motor speed rating
Motor insulation type
F5005
Set the rated current, frequency and speed as well as insulation type for the motor.
Code No.
Function Name
F5002
Motor current rating
F5003
Motor frequency rating
F5004
Motor speed rating
F5005
Motor insulation type
※Typical values have been entered for each motor model.
● Normally, please set the motor rated values. When these values cannot be set, the auto detection results and the controls of speed,
torque and position will become worse.
Note 1: the setting values are interlocked with the settings of motor poles, voltage and capacity (F5001). Therefore, when
F5001 is changed, F5002~F5005 will automatically set the standard values according to F5001.
Note 2: The above setting values cannot be used in V/f mode (F1001=1, 40).
Note 3: In speed control mode, when operating speed exceeds the rated speed, it will be flux-weakening control.
F5006
The motor's rated voltage during auto tuning of
motor parameters
The function code used for special motor and in other occasions during auto detecting of motor parameters.
Code No.
Function Name
F5006
The motor's rated voltage during auto
tuning of motor parameters
When the rated voltage of F5001 is used, the setting is not required. (F5006=0)
Rated motor slip
F5007
Set the rated slip ratio of the motor in use.
The standard for addition and correction of slip ratio in auto torque increase (F2007=2).
When the motor is loaded, add and correct the slip ratio to control the speed decrease.
Code No.
Function Name
F5007
Rated motor slip
Please calculate with the following formula.
120×Reference frequency (F1006)
Synchronized speed = ————————————————
Motor poles P (poles in F5001)
Synchronized speed-Rated speed (F5004)
Rated motor slip ratio = —————————————————×100%
The setting of motor parameter auto tuning range
F5008
The function to set the range of valid detecting constant according to the factory presets during motor parameter auto detection
(F1001=10, 11).
Code No.
Function Name
F5008
The setting of motor parameter auto
tuning range
Note: When the range of motor parameter auto detecting results is extended, the controls of speed, torque and position
and auto torque increase may become worse. Please change the setting during auto detecting errors of special
motors and motor parameters.
F5009
Motor stator resistance
0.1~999.9
About 30 — 110% of the inverter current rating
10~400Hz
0~24000 rpm
1:
Type A
Type
2:
E
Type
3:
B
Type
4:
F
5:
Type
H
0: Use voltage selected by F5001
100-460V (voltage of F5001 is noneffective)
Synchronized speed
- 146 -
Data Content
Data Content
Data Content
0~50%
Data Content
No range
0:
50~300%
Factory
Setting Resolution
Presets
0.1A
1Hz
1rpm
1
Factory
Setting Resolution
Presets
1V
0
Factory
Setting Resolution
Presets
0.1%
2
Factory
Setting Resolution
Presets
0.1%
200