Useful menu options

The menu map for all the menu driven controls that are
accessible at the control panel are detailed in Appendix A.

Panel Buzzer

¨
It may be necessary during commissioning to disable
the panel buzzer. It is possible to selectively switch the
disablement, fault, fire and supervisory buzzer sound
Off or On. It is important to ensure that the buzzers are
switched On for normal operation after commissioning.
Press Menu On/Off button and then select [Test/Eng],
[UserCode] and enter the Engineering password
(PIN), this is only necessary if an Engineering
password has been set up. Select <etc> [Config],
[Buzzer] this will allow selection of [Disable],
[Fault], [Fire] or [Supervis] signifying total buzzer
disablement or disablement of local sound signal for
this type of event and then select [On/Off] and
[Enter].
"
There is no indication given at the panel of
buzzer disablement.

Software version

The software version of the panel can be displayed by viewing
the status of the master control board/card.
To check the software on the master control board/card: Press
Menu On/Off button and then select [Info], momentarily press
<etc> to select [Status] -> [Card] and enter Card number 0,
which is the Main Control Card / Master Control Board and select
[Enter]. The display will show software version number and date
of release.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Vigilon (EN & BS) Compact (VA) panels
Password or Personal
Identification Number
"
The terms Password, PIN, Usercode and
Access code mean the same and are used
interchangeably.
A password or personal identification number (PIN) restricts
access to the controls available to the user at the Control panel.
There are three access levels to the controls these are access
level 1, 2 and 3. Access
level 1 only allows the cycling through
multiple events on the screen using the two buttons on the outer
door.
¨
Access level 2a is for the CUSTOMER, here the
person responsible for the system can access essential
controls using the panel door key
¨
Access level 2b is for the CUSTOMER - here the
person responsible for the system can access essential
controls and some configuration menu options using
the panel door key plus customer PIN.
¨
Access level 3 is for the ENGINEER - here the person
responsible for the system can access essential controls
and all system menu options using the panel door key
plus Engineer PIN.
¨
There is another password (PIN) that changes daily,
which is available to the servicing organisation. This
daily password provides the same access to controls as
the Engineers' PIN. The daily PIN is only used when
the Engineer's PIN is not known.
"
Always make a note of the Customer and
Engineering passwords or PINs once they are created.
Ensure the Customer password or PIN is passed on to
the person responsible for the fire alarm system on site.
39