Notifier INSPIRE E10/E15
Fire Alarm Control Panels
Installation Instructions

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Notifier INSPIRE E10

  • Page 1 Notifier INSPIRE E10/E15 Fire Alarm Control Panels Installation Instructions...
  • Page 2: Table Of Contents

    ID²Net Network Module Panel Parts Serial Communication Interface Module Parts of Notifier INSPIRE Panels 4 Channel I/O Module Unpacking a Notifier INSPIRE E10 Panel FARE / FRE Module Unpacking a Notifier INSPIRE E15 Panel Communication Dual (FAT/FBF) Module Extension and Options...
  • Page 3 Notifier INSPIRE E10/E15 Control Panels - Installation instructions RELATED DOCUMENTS ABBREVIATIONS In addition to this guide refer to: Control and Indicating Equipment Operating Manual INSPIRE E10/E15 Control Panel (Part Central Processing Unit † number HOP-338-9EN) 10U size Panel enclosure Commissioning Manual INSPIRE E10/E15 Control Panel 15U size Panel enclosure †...
  • Page 4: Introduction

    CIE comply with class 3k5 of EN 60721-3-3. SYSTEM DESIGN AND PLANNING It is assumed that the system, of which the Notifier INSPIRE E10/E15 equipment (Control and Indicating Equipment CIE) is a part, has been designed by a competent fire alarm system designer in accordance with the requirements of local codes of practice that are applicable.
  • Page 5: System Equipment

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions SYSTEM EQUIPMENT The INSPIRE E10/E15 Control panel is designed for use with Notifier by Honeywell range of addressable detector, control and monitoring modules and addressable call points. It supports both OPAL and CLIP loop polling protocols.
  • Page 6: How To Use This Guide

    Introduction HOW TO USE THIS GUIDE This Installation Guide is intended to provide you with simple guidelines on how to install the INSPIRE E10/E15 Control panel quickly and safely. The modular design of the INSPIRE E10/E15 Control panel offers configurations to meet the requirements of different markets.
  • Page 7: Pre-Installation Check List

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions Pre-installation Check List Before installing a INSPIRE E10/E15 Fire alarm equipment you must first ensure that the following criteria have been met. Failure to do this may not only result in damage to the equipment, but may also cause problems when commissioning the equipment or adversely affect its performance.
  • Page 8 Pre-installation Check List CHECKING YOUR PANEL FOR DAMAGE It is important to check all supplied equipment for damage before proceeding with the installation! Before attempting to install the INSPIRE E10/E15 Control panel, or other equipment, you must do the following: After removing the INSPIRE E10/E15 Control panel, modules other related equipment from its packaging, and before you proceed with installing it in its chosen location, check for any damage that may have occurred...
  • Page 9: Installation Overview

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions Installation Overview The panel range is designed for mounting onto an internal wall of a protected building and is not suitable for mounting on to external wall. Install the panel enclosure in accordance with the instructions to be found in this guide.
  • Page 10: Cables

    Cables Cables All wiring must comply with local wiring regulations. Note also the requirements for cabling and interconnection of a fire detection and alarm system. For information on wiring inputs and outputs refer to the appropriate module and wiring to their terminals. CABLING INSTRUCTIONS Cables must be brought into the enclosure using the 20 mm cable entry points provided on the top and rear of the panel enclosure.
  • Page 11 Notifier INSPIRE E10/E15 Control Panels - Installation instructions CABLE TERMINATIONS This section provides guidance on where to bring cables into the INSPIRE E10/E15 Control Panel enclosure for ease of termination. Ensure the following requirements are met: The mains supply must be brought into the INSPIRE E10/E15 Control panel such that the cable path to the Mains Terminals block is kept as short as possible.
  • Page 12 Cables RECOMMENDED CABLES The cable length of a loop circuit is precisely calculated using the Battery Standby Calculator feature in the 'CLSS Configuration tool'. The cable length is dependant on the loading of devices connected to each loop of a Control panel.
  • Page 13 Notifier INSPIRE E10/E15 Control Panels - Installation instructions NETWORK COPPER CABLES AND DISTANCES FOR ID2NET Cable Type Recommended operating distance Region(s) Prysmian FP200 Flex (1.5mm2) 850m Draka Firetuf FDZ2ER (1.5mm2/2.5mm2) 1200m AEI MICC 2L1.5 (1.5mm2) 1200m AEI Firetec F2CxxE (1.00mm2 / 1.5mm2) 1350m Prysmian FP200 Gold (1.5mm2)
  • Page 14 Cables EMC CONSIDERATIONS  Good quality fire industry cable must be used incorporating drain wires or screens. The drain wires or screens must be earthed within the enclosure. Use cable manufacturers recommendations for adequate earthing of the drain wires or screens along with the procedures in this document.
  • Page 15: Panel Technical Data

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions Panel Technical Data STANDARDS Designed to: EN54-2 (see also option with requirements clauses) † EN54-4 † PANEL FEATURES Display - 10” (25.4cm) Touch-screen graphical colour display, 1280(RGB)×800 pixels, with back illumination. †...
  • Page 16 Controls - momentary - action push buttons are provided for the following functions: † SILENCE/RESOUND, SILENCE BUZZER and RESET in addition to the on-screen buttons Buzzer to draw attention when an event has occurred. Buzzer volume: ≥60 dBA at 1m †...
  • Page 17 Notifier INSPIRE E10/E15 Control Panels - Installation instructions Total Weight of E10 and E15 panels † Panel with 3 Modules as Add weight of Batteries Add weight of supplied but without batteries (2 required) additional Modules 11.3 kg 4.05 kg per 12 V, 12 Ah battery...
  • Page 18 Panel Technical Data ELECTRICAL The Panel’s power supply equipment (PSE) provide power requirements of the local display and fitted modules and their external circuits. In addition, the panel contains a battery charger circuit for the mains-fail, back-up batteries. All the power is normally derived from an external AC mains power source. When the mains power supply is not available, the standby batteries automatically supply the power requirements for a limited period, this period being determined by the requirements of the local fire standards.
  • Page 19 Notifier INSPIRE E10/E15 Control Panels - Installation instructions Battery current with mains disconnected is dependent on the system configuration and current during alarm. † Battery charging Current: 0.8 A (12 Ah), 1.6 A (24 Ah) and 2.5 A (38 Ah) †...
  • Page 20 Panel Technical Data EN54-4 DATA Notifier INSPIRE E10 panel Notifier INSPIRE E15 panel with: with: 240W PSU 480W PSU (AC to DC converter) (AC to DC converter) 12V BATTERY CAPACITY 12 Ah 24 Ah 24 Ah 38 Ah Charger Input Current (maximum) 0.72 A...
  • Page 21 Notifier INSPIRE E10/E15 Control Panels - Installation instructions PSU 240W AND 480W Note the DC OK relay contact pins 13 and 14 on the PSU are not for general use. The DIN rail mounted single-phase-input power supply provides a floating, stabilized and galvanically separated SELV/PELV output voltage.
  • Page 22: Notes To Installer

    Notes to Installer Notes to Installer RECOMMENDATION The installer must follow the general requirements of local code of practice relating to fire detection and alarm systems for buildings. The installer must also follow the relevant local wiring regulations. PARTS FOR INSTALLATION LATER To prevent the possibility of damage or dirt degrading the performance or appearance of the products, the installation of second fix parts such as doors, modules and battery must be delayed until all major building work in the area is complete.
  • Page 23 Notifier INSPIRE E10/E15 Control Panels - Installation instructions CABLE TYPE AND ROUTING Appropriate attention must be given to ensure the correct cable type is installed in accordance with ‘as fitted drawings’, site specific information and recommendations of national standard and local regulations. The cables must be installed using cable manufacturers recommended fixing and accessories.
  • Page 24: Panel Parts

    Panel Parts Panel Parts NOTIFIER INSPIRE PANEL RANGE HOP-131-206 Fire Alarm Control Panel Inspire E10 6S 240W 10" 2-loop HOP-134-412 Fire Alarm Control Panel Inspire E15 12S 480W 10" 2-loop BATTERY (NOT SUPPLIED, OPTIONAL EXTRA) NP12-38 38 Ah 12 V Sealed Lead Acid Battery (for an E15 enclosure only) NP12-24 24 Ah 12 V Sealed Lead Acid Battery...
  • Page 25 Notifier INSPIRE E10/E15 Control Panels - Installation instructions SPARE PSU HOP-501-240 PSU 240 W (spare part) HOP-501-480 PSU 480 W (spare part) 2-SLOT MODULE CARRIER AND LINK MODULE HOP-202-102 2-slots Module Carrier supplied with a (option for extension Link Module...
  • Page 26: Parts Of Notifier Inspire Panels

    Parts of Notifier INSPIRE Panels The Notifier INSPIRE E10/E15 range of Control panels are modular design to make installation easier. Each panel is supplied in the following parts: a back box enclosure, standard modules and a door assembly, plus spare parts and the batteries are optional extra not supplied with the panel.
  • Page 27: Unpacking A Notifier Inspire E10 Panel

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions UNPACKING A NOTIFIER INSPIRE E10 PANEL Item Description Door assembly  Backbox  Label assembly Side Covers     Charger Module  Dual Loop  CPU Module  NOT SUPPLIED ...
  • Page 28: Unpacking A Notifier Inspire E15 Panel

    Parts of Notifier INSPIRE Panels UNPACKING A NOTIFIER INSPIRE E15 PANEL Item Description  Door assembly  Backbox assembly  Charger Module  Label Dual Loop Module     CPU Module  NOT SUPPLIED  Typical option 12 V 24 Ah CHARGER Battery X 2 ...
  • Page 29 Notifier INSPIRE E10/E15 Control Panels - Installation instructions Spare parts supplied with the panel Item Description   Door key  x2 (E10) x2 (E10)  FIRE FEUER FUEGO FAULT STÖRUNG FAUTE CULPA Spacers DÉFAUT DU SYSTÈME  SYSTEM FAULT...
  • Page 30: Extension And Options

    Parts of Notifier INSPIRE Panels EXTENSION AND OPTIONS Item Description A standard E10/E15 Notifier Inspire panel can be extended to provide Optional modules additional functionality and for this there are spare slots available in  Dual Loop Module (Purple) the module carrier to accommodate optional modules. The module carrier can also be extended by 2-slots using an optional 2-slot Serial Comm Module (White) ...
  • Page 31: Panel Installation

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions Panel Installation BACKBOX SPACERS Ensure either the 8 mm or 14 mm keyhole spacers   MOUNTING HEIGHT and round hole spacers supplied are fitted to  the backbox , to offset it from the wall. Normally ...
  • Page 32: Surface Mount

    Panel Installation SURFACE MOUNT A Notifier INSPIRE E10/E15 panel can be surface mounted onto a flat wall using suitable fixtures and fittings, whilst considering the weight of a fully assembled panel with batteries, see Technical Data for weight information. As a general recommendation for types of wall surfaces ensure assessments are made and suitable fixtures and fittings are used to hold the panel assembly.
  • Page 33: Side Covers

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions SIDE COVERS   A surface mounted Notifier INSPIRE E10 panel requires Right and Left Side Covers to be fitted to the panel   backbox. Knock out the 8 keyholes from both sides of the backbox. Ensure the Right Side Cover is in the ...
  • Page 34: Wall Recess For Semi Flush Fixing A Panel

    WALL RECESS FOR SEMI FLUSH FIXING A PANEL A Notifier INSPIRE E10/E15 panel can be semi flush mounted into a wall recess using a Semi Flush Surround mounting kit (HOP-238-110) for an E10 enclosure and kit (HOP-238-115) for an E15 enclosure.
  • Page 35 Notifier INSPIRE E10/E15 Control Panels - Installation instructions SEMI FLUSH FIXING AN E10/E15 PANEL These procedures semi flush mounting an E10/E15 panel into a wall.  Check the wall recess is of the correct size, see previous page for information on recess.
  • Page 36: Front Door

    Panel Installation FRONT DOOR REMOVING THE FRONT DOOR Once the backbox of an Notifier INSPIRE E10 / E15 panel Ensure Mains and Battery supplies are powered is secured to a wall surface or semi flush mounted to a down. wall, the Front Door can be attached to the backbox using First, disconnect the cable from the CPU Module two quick-release-type hinges.
  • Page 37: Module Carriers And Slots

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions MODULE CARRIERS AND SLOTS As standard the E10 / E15 panel enclosures have either a 6 slots / 2 x 6 slots module carriers respectively as standard. The Termination module (A) has cable connections for power and battery. The Row link modules (B) connects first row to a second row of the module carriers.
  • Page 38: Location Of Modules In Carrier Slots

    Panel Installation LOCATION OF MODULES IN CARRIER SLOTS It is required that the Charger module is always fitted in Slot 1 of the module carrier and CPU Module fitted in Slot 2 of Module Carrier. IMPORTANT - panel range. Module: Module: Modules: - Loop Opal 2X...
  • Page 39: To Fit Terminal Blocks

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions TO FIT TERMINAL BLOCKS TO REMOVE TERMINAL BLOCKS There are two 5-way terminal blocks supplied with The UPPER and LOWER 5-way terminal blocks can be  each module. prised out and removed from the Module Carrier ...
  • Page 40: To Fit Protection Cover Over Backbox

    Panel Installation TO FIT PROTECTION COVER OVER BACKBOX Dust generated from building work processes may enter parts inside a backbox mounted on a wall. To prevent dust getting into the backbox, use the cardboards in panel packaging to make a dust cover for the backbox.
  • Page 41: To Fit A Module

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions TO FIT A MODULE TO REMOVE A MODULE   Here is how to fit a Module into a slot of a Module Here is how to remove a Module from a slot in the ...
  • Page 42: Cable Screen To Earth

    Panel Installation CABLE SCREEN TO EARTH CABLE ROUTING Here is how to connect the screen of an external Illustrated below is a cut out side view of an E15 panel  cable coming into the panel enclosure. enclosure showing how cables are routed to the ...
  • Page 43: Cable Length And Label

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions CABLE LENGTH AND LABEL TERMINAL NUMBER LABEL  Each incoming wire must be fitted with a Label tag  Take one strip of label . Cut the label in half to ...
  • Page 44: Module And Terminal Blocks Identification

    Panel Installation MODULE AND TERMINAL BLOCKS IDENTIFICATION  To ease wiring of external cables to respective terminal blocks you will need to decide in which slots of module    carriers each module is to be located. Each module is colour coded and the respective colour coded label from the label set must be fitted to the 1 Loop 1 OUT +VE module carrier, as illustrated.
  • Page 45: Loop (Opal X 2) Module

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions LOOP (OPAL X 2) MODULE Dual Loop module has the capability of 2 loop † circuits that can accept Opal/Clip device Ability to measure loop series and parallel † 1 Loop 1 OUT +VE resistances.
  • Page 46: How Loop Circuits Get Numbered

    Panel Installation HOW LOOP CIRCUITS GET NUMBERED The loop circuits are interpreted sequentially from left to right of module carrier. So the first loop module fitted to the left slot of the module carrier has Loop circuit 1 with other loops to the right sequentially numbered. The E15 panel has two rows of module carriers, here the second row of loop numbers continue from the first row.
  • Page 47 Notifier INSPIRE E10/E15 Control Panels - Installation instructions channel' or 'Fault input channel' LOOP BATTERY CALCULATOR Module's Input or Output 'channel' can be It is strongly recommended that the ‘Loop Battery associated with 'Detection Zone', 'Alarm Zone' calculator' is used to ensure that an INSPIRE system or 'Control Zone'.
  • Page 48: Opal Devices

    Panel Installation OPAL DEVICES The Opal devices listed below are those that are commercially available. Check to ensure respective device is available for selection in the CLSS Configuration Tool and for subsequent use with the 'Battery Calculator' to ensure their correct operation with the Notifier INSPIRE system. Detectors NFXI-OPT Opal Optical smoke detector, built-in isolator (White)
  • Page 49 Notifier INSPIRE E10/E15 Control Panels - Installation instructions NFXI-DKMB Manual Call Point, DIN Class B, with built-in isolator (DE) (Blue) NFXI-DKMG Manual Call Point, DIN Class B, with built-in isolator (DE) (Yellow) NFXI-DKMR Manual Call Point, DIN Class B, with built-in isolator (DE) (Red)
  • Page 50 Panel Installation Input Output Modules M700X Loop Isolator Module, plug-in screw connections M701 Single Output Module - addressable, direct decade address entry, with built-in isolator M701-240 Single 240 V AC / 5 A Output Module - addressable, direct decade address entry, surface mount box, tri-colour LED's, with built-in isolator M701-240-DIN Single 240 V AC / 5 A (DIN Rail Mount) Output Module - addressable,...
  • Page 51 Notifier INSPIRE E10/E15 Control Panels - Installation instructions NFXI-ASD12-HS FAAST LT Double Knock Notifier Loop Single channel loop connected FAAST LT aspirating unit fitted with 2 HSS detectors and bases. Also includes built in filters. Requires 24V power supply. NFXI-ASD12-HS-EB FAAST LT200 double knock Notifier c/w EB Single channel loop connected FAAST LT aspirating unit fitted with 2 HSS detectors and bases.
  • Page 52: Fire Protection Equipment (Fpe)

    Panel Installation FIRE PROTECTION EQUIPMENT (FPE) An M721-SST Interface is used to connect to Fire Protection Equipment. Loop Sensor Ensure end-of-line devices supplied with the M721-SST INTERFACE are fitted to its I/O lines. Fire Protection Equipment (FPE) M721-SST FPE application: INTERFACE - Fixed fire fighting system ACTION...
  • Page 53: Cpu Module Notifier

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions CPU MODULE NOTIFIER In VdS installations it is forbidden to use un-monitored relay contacts for fire alarm signal transmission purposes. A specific module is provided for this purpose. 3 Relay Fire NC There is a 36 V DC supply at 1 and 2, is not shown.
  • Page 54 Panel Installation WIRING External External Equipment Equipment    Relay contacts used to control external equipment in the event of a Fire condition.  Relay contacts used to control external equipment in the event of a Fault condition.  ...
  • Page 55: Charger Module

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions CHARGER MODULE Charger module is colour coded Green † Dimensions H-130 mm x W-28 mm x D-117 mm † Charge and discharge current monitoring † Under Voltage Lockout that switches the battery †...
  • Page 56: Id²Net Network Module

    Panel Installation ID²NET NETWORK MODULE Optional plug-in adapters to convert to Optical Fibre † Any combination of RS-485 / Optical Fibre allowed † Module can be given a 40 character software label for † display on panel HMI COPPER NETWORK CABLE 4 RS485 #B Pin B 5 RS485 #B Pin A See approved lists of cables used for the wiring of...
  • Page 57 Notifier INSPIRE E10/E15 Control Panels - Installation instructions HOW TO ADD MULTI MODE FIBRE TO AN ID2NET MODULE The Net Converter Fibre Multi Mode (HOP-608-200) consist of two identical PCB assemblies that must be fitted  . inside an ID2NET module to permit Fibre ST connections. To fit the PCBs inside an ID2NET follow steps ...
  • Page 58 Panel Installation ID2NET NETWORK COPPER AND MULTIMODE FIBRE WIRING 1 2 3 4 5 6 7 8 9 10 1.2Km or more # 2Km Multimode copper cable distance fibre cable RS485 #A Pin B RS485 #A Pin A Rx Tx Rx Tx Rx Tx Rx Tx...
  • Page 59: Serial Communication Interface Module

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions SERIAL COMMUNICATION Serial Communication Module is colour coded White † Dimensions H-130 mm x W-28 mm x D-117 mm † INTERFACE MODULE Monitors communication faults † Module can be given a software label for †...
  • Page 60 Panel Installation WIRING TO A REPEATER PANEL WIRING TO CLSS GATEWAY IDR6A Repeater panel CLSS Gateway Cable distance of (002-452) up to 1.2Km maximum Maximum of up to 15 Repeater panel COMM Serial COMM Serial...
  • Page 61: Channel I/O Module

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions 4 CHANNEL I/O MODULE The cable length of an Output circuit is precisely calculated using the Battery Standby Calculator feature in the 'CLSS 1 Aux. DC Out 24 V Configuration Tool'. 2 Aux. DC Out GND...
  • Page 62 Panel Installation WIRING TO INPUT AND OUTPUT CIRCUITS cable length 100m recommended maximum 24V dc black Alarm Output EOL - O (Part number 808624) Earth bar EOL - O EOL - O 808624 808624 V0100R001 V0100XXXX Fault Input 1 KΩ 10 KΩ...
  • Page 63: Fare / Fre Module

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions FARE / FRE MODULE Interface to FRE equipment (e.g. Dialler) † FRE input is supervised for open and short circuit † Interface to Key Safe Adapter for Key Safe (VdS2105) † the Module can be given an identification label †...
  • Page 64 Panel Installation TECHNICAL DATA 24V Aux. Output Voltage and Current 24 V ± 5%, max. 1 A FARE Interface Voltage and Current 24 V ± 5%, max. 0.17 A Min. Input high level voltage : ≥ 2.0 V Acknowledge Input Max.
  • Page 65 Notifier INSPIRE E10/E15 Control Panels - Installation instructions WIRING TO EQUIPMENT Fire Alarm Routing Equipment including PSU The FRE equipment MUST be Fault Routing installed directly next to the FARE Activ. INSPIRE panel, the CIE. Equipment +24V FARE Ack. FARE GND...
  • Page 66: Communication Dual (Fat/Fbf) Module

    Panel Installation COMMUNICATION DUAL FAT/FBF Module is colour coded Light Blue † Dimensions H-130 mm x W-28 mm x D-117 mm † (FAT/FBF) MODULE Configurable via 3rd party software for FAT/FBF † applications 1 UB1+ the Module can be given an identification label †...
  • Page 67 Notifier INSPIRE E10/E15 Control Panels - Installation instructions WIRING TO DE EQUIPMENT - FAT/FBF Bus1 SIO1- SIO1+ UB1- FAT4000 UB1+ 10-way ribbon cable Bus2 FBF4000 SIO2- FBF4000 optional SIO2+ UB2- UB2+ Cable distance up to 800m, Type J-Y (St) Y n x 2 x 0,8 mm Ensure ‘Bus1’...
  • Page 68 Panel Installation WIRING TO DE EQUIPMENT - 2 FAT Bus1 SIO1- SIO1+ UB1- FAT4000 UB1+ 10-way ribbon cable Bus2 FBF4000 SIO2- FBF4000 optional SIO2+ UB2- Maximum loop UB2+ cable length 800 m Type Bus1 J-Y (St) Y n x 2 x 0,8 mm SIO1- SIO1+ UB1-...
  • Page 69: Mains Supply

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions Mains Supply marked ‘L’. Connect the Protective Earth ‘PE’ wire to termination point marked with an Earth symbol. Ensure mains cable gland used provides IP30 It is important to open and lock out the main protection.
  • Page 70: Battery Installation

    Battery installation Battery installation The YUASA 12V NP series batteries are recommended for Notifier INSPIRE E10 and E15 panel range. The E10 panel enclosure can accommodate 12Ah and 24Ah batteries, while the E15 panel enclosure can additionally accommodate 38 Ah batteries. Note the 12 Ah battery have faston tabs for terminals for battery cable connection.
  • Page 71 Notifier INSPIRE E10/E15 Control Panels - Installation instructions How to connect the 12V 24 Ah batteries The battery manufacturer's recommendations on battery handling, storage, maintenance charging, operation and disposal must be taken into consideration. Secure the battery and link leads to the battery terminals with the bolt, washers, spade connector supplied.
  • Page 72 Battery installation How to connect 12V 12 Ah and 12V 38 Ah batteries The battery manufacturer's recommendations on battery handling, storage, maintenance charging, operation and disposal must be taken into consideration. Secure the battery and link leads to the battery terminals with the bolt, washers, spade connector supplied. ...
  • Page 73: Fitting A Language Film Insert

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions Fitting a language film insert Find the language film set supplied with the panel. Select the required language film, which is dependant on the country and region. The text on the film is made visible to the user when the corresponding event LED or button LED on the panel fascia is lit.
  • Page 74: Fitting The Hmi Cable

    Fitting the HMI cable Fitting the HMI cable  Locate the HMI cable (which is also referred to as OCulink cable) , which is taped to the inside of the panel   door . Route the HMI cable from the door into the backbox. Press the button 'a' on the HMI cable connector ...
  • Page 75: Commissioning

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions Commissioning The commissioning process require each Notifier INSPIRE E10/E15 Control panel based system to be powered up to an operational state ready for configuration, refer to the Commissioning instructions manual (HOP-138- 8EN) for detials on first time commissioning.
  • Page 76: Configuration And System Test

    Configuration and System Test Configuration and System Test The CLSS Configuration Tool must be used to configure the INSPIRE system to site specific requirements and to national and local regulations, see CLSS Configuration Tool user guide. Once an INSPIRE system is fully configured using the CLSS Configuration Tool, the tool must be connected an INSPIRE panel and systems configurations synchronised.
  • Page 77: Maintenance

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions Maintenance GENERAL This log book should be used for recording day to day events in the system , it should be used to record service and maintenance work visits. ROUTINE TESTING In order to ensure that the system is fully operational it must be routinely tested in accordance with the requirements of EN54-14, national code of practice and local requirements.
  • Page 78: Standards

    EN54-2: Clause 13.7 requirements The Notifier INSPIRE E10/E15 Control panel is designed with fall back fire line so that in the event of a processor failing and in the event of a fire detection, the General Fire LED and panel buzzer are activated and if the FARE/FRE module is fitted then the Fire Routing output will be activated.
  • Page 79: Option With Requirements En54-2

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions OPTION WITH REQUIREMENTS EN54-2 CONTROLS Delays to outputs CLAUSES Outputs C², E² and G¹ 7.11.1 Provision to switch on and switch off the delayed operation of outputs ³ 7.11.2 Dependencies on more than one alarm signal Type A dependency 7.12.1...
  • Page 80 Standards Output type C 7.10.3 Fault monitoring of fire protection equipment 7.10.4 Output to fault warning routing equipment DISPLAYS Alarm counter 7.13 Fault signals from points ¹ Note : For VdS Installations not permitted. ² Note : For VdS installations not permitted in combination with a manual call point. ³...
  • Page 81: Ecodesign Requirements For Electronic Displays

    Notifier INSPIRE E10/E15 Control Panels - Installation instructions Appendix A ECODESIGN REQUIREMENTS FOR ELECTRONIC DISPLAYS Open the panel door using the key. Follow the steps below to dismantle the assembly to gain access to the Display for removal or maintenance.