Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 147

For the fire alarm systems
Table of Contents

Advertisement

Installation instructions
new IO Card (EN54)
(VIG-IOC-DOM)
This new Input Output (IO) card (part no. VIG-IOC-DOM) is
designed for installation in EN54 Vigilon analogue addressable
fire panels and Network node:
Vigilon Fire Panels
VIG1
VIG1-NET
VIG2
VIG2-NET
VIG3
VIG3-NET
VIG4
VIG4-NET
Vigilon Network (Terminal) Node
VIG-NODE.
new IO card replaces existing IO cards
The new IO card combines the functions of and will replace the
existing IO cards:
VIG-IOC-PRT
VIG-IOC-ASCOM
VIG-IOC-UFD
VIG-IOC-UNI
The existing IO cards are no longer available.
new IO Card (EN54) 4188-777 issue 3_11/05
Specification
Overall size
148mm height x 100mm
width
Node address range
1 to 31
Baud
1200, 1800, 2400, 3600,
4800, 7200, 9600 and 19200
(When installed as an
additional IO card)
RS232 (Port 0)
10m cable distance
RS485 (Port 1)
1.2Km cable distance
Weight
72g (approximate)
Operating temperature 0°C to 45°C
Storage temperature
-10°C to 55°C
Relative humidity
up to 90%
(non condenscing)
"
There is no need to switch between the
RS232 and RS485 ports as they are both available for
simultaneous use.
IO card installation and associated
terminals
The diagram below shows the associated terminals for
standard IO card when it is installed in the backplane of
panel/node.
RS485 (Port 1)
-ve 5V +ve 0V
Terminal card
Checks
¨
Set the rotary switch SW2 to a required function.
¨
Ensure all DIP switches SW1 are set to the Off
position before installing the IO card in socket P2 of
the backplane
¨
Connect the 20 way ribbon cable from DKC
connector P4 to the IO card socket P2.
¨
One additional IO card can be fitted into the
backplane spare socket P7 of the control panel and
up to four into the backplane sockets of the Network
node.
When installing an additional IO card it is important
to set its DIP switches SW1 to the required baud rate
and node address and the rotary switch SW2 to the
required function before installing the card in a spare
socket of the backplane.
by Honeywell
RS232 (Port 0)
Tx CTS Rx RTS
1