Generic Commissioning instructions

Zone Tasks

OUTSTATION IN ONE ZONE ONLY
DEVICES ASSIGNED
TO ZONE 'A'
HEAT DET.
SMOKE DET.
LOOP 1
MCP
I/O
DEVICES ASSIGNED
TO ZONE'A'
HEAT DET.
SMOKE DET.
LOOP 2
MCP
I/O
via TEST/ENG menu
TIME
BLOCK
¨
There can be up to 128 Zones of which the first 64 are for standalone system and remaining zones for network use.
The number of Zones for standalone system can be re-configured via the commissioning tool.
¨
a zone is a collection of devices, sharing a common label
¨
an device can only be assigned to one zone
¨
a Zone task may be used to control the display of fire messages, to provide:
Common zone label only (this is the default).
label of first device in fire
or all individual device labels.
¨
a zone can provide 3-level sensing:
Prefires
Fires
Superfires
¨
sensors can be configured to provide coincidence operation using a combination of all 3 levels if required
¨
up to 8 permutations of fire detection (Zone tasks) may be configured per zone
¨
a zone task can be made to trigger a command build or a range of command builds, (this is done in the zone set up
menu)
¨
the same command build can be triggered by different tasks within a zone
¨
disabling a zone will disable the sensors within that Zone
¨
disabling a zone via a time block disables the tasks performed by the zone.
¨
all devices default to zone 1
122
DISPLAY ALL
INDIVIDUAL
ALL DEVICES THAT
DEVICE LABELS
GO INTO FIRE
WILL TAKE THIS
ROUTE
DEFAULT
TOTAL OF 128
w SENSOR x PRE FIRE y FIRE z SUPER FIRE
ZONES
PER PANEL
w SENSOR x PRE FIRE y FIRE z SUPER FIRE
ZONE
'A'
w SENSOR x PRE FIRE y FIRE z SUPER FIRE
w SENSOR x PRE FIRE y FIRE z SUPER FIRE
w SENSOR x PRE FIRE y FIRE z SUPER FIRE
w SENSOR x PRE FIRE y FIRE z SUPER FIRE
w SENSOR x PRE FIRE y FIRE z SUPER FIRE
w SENSOR x PRE FIRE y FIRE z SUPER FIRE
DISPLAY
FIRST
DEVICE LABEL
DISPLAY
COMMON ZONE
LABELS ONLY
TASK NUMBER 1
TASK NUMBER 2
TASK NUMBER 3
TASK NUMBER 4
TASK NUMBER 5
TASK NUMBER 6
TASK NUMBER 7
TASK NUMBER 8
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
TO ALL REPEATS
ON LOCAL PANEL
OUTPUT TRIGGER
TO COMMAND BUILD 'X'
OUTPUT TRIGGER
TO COMMAND BUILD 'X'
OUTPUT TRIGGER
TO COMMAND BUILD 'X'
OUTPUT TRIGGER
TO COMMAND BUILD 'X'
OUTPUT TRIGGER
TO COMMAND BUILD 'X'
OUTPUT TRIGGER
TO COMMAND BUILD 'X'
OUTPUT TRIGGER
TO COMMAND BUILD 'X'
OUTPUT TRIGGER
TO COMMAND BUILD 'X'