Generic Commissioning instructions

Power up

Battery supply
¨
A battery lead supplied in the spares pack must be
fitted to the Power supply board, connector P7 labelled
Bat1. Next install the batteries inside the enclosure,
which requires removal of battery brackets from the
panel and installation of the batteries in correct
orientation, standing on the small side with terminals at
the top facing outwards. Secure the batteries by
refitting the battery brackets.
¨
Switch On the mains supply to the panel and then
make the connection to the battery.
Battery lead connection
on PSU board P2 Bat1
Panel with doors open
Battery brackets
Secured with two screws
"
The panel makes use of sealed lead acid type
batteries which can have a useful life of up to 5 years
from the date of manufacture. It is strongly recommended
that batteries are replaced after 4 years of use. Batteries
must be disposed of as per recommendation made by
battery manufacturer.
&
Always use the recommended
replacement battery. As there is a risk of an
explosion if incorrect batteries are used.
PANEL
P3
43V
FS6
1A P7
BAT1
-
Black
- +
- +
36
PSU
Battery brackets
Secured with two nuts
PSU BOARD
Y1 Y2 G1
+
Red
2 - 12V 12Ah battery
Mains supply
Dedicated mains supply
from consumer unit
5A Unswitched fused
spur unit
PANEL
FS3 3.15A(T)
Mains fuse
¨
Ensure the mains supply cable enters the equipment via
a dedicated cable entry point, which is located adjacent
to the mains terminal block and is also segregated from
any loop wiring.
¨
The mains supply to the fire alarm control and
indicating equipment must be via a 2-pole unswitched
fused spur unit (Disconnect device).
A Disconnect Device should be available as part of the
building installation, fitted near the panel. The contacts
of the disconnect device should have a separation of at
least 3mm.
&
Hazardous voltage remains after
operation of a protection fuse. Take appropriate
action to guard against the risk of equipment having
exposed live mains supply.
¨
Each fire alarm equipment fused spur unit must be
from a dedicated switch or protective device at the
local mains supply distribution board, which should be
clearly labelled FIRE ALARM - DO NOT SWITCH
OFF.
Indicators on the power supply board
Description
Y1
(yellow)
Normal condition
(no faults in the
system)
Mains out of limit
24VDC failure only
Battery 1 failure
only
Battery 1 and
24VDC failure
43VDC failure only fast flash
No power to PSU
Earth fault only
On
Note on initial power up all three LEDs on the PSU
will switch on for approximately 1 second duration.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
N E
L
P2
DANGER
Y2
G1
(yellow)
(green)
fast flash
slow flash
fast flash fast flash
slow flash fast flash
slow flash fast flash
fast flash
On
On

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gent viglion compact voice alarmGent viglion compactGent viglion bs

Table of Contents