Useful menu options

The menu maps of all the menu options that are accessible at the control panel are detailed in
Appendix A.

Panel Buzzer

¨
It may be necessary during commissioning to disable the panel buzzer. It is possible
to selectively switch the disablement, fault, fire and supervisory buzzer sound to Off
or On. It is important to ensure that the buzzers are switched On for normal operation
after commissioning.
# - will appear if a PIN is setup.
Press Menu On/Off button and then select [Test/Eng] -> [UserCode]# and select
<etc> [Config], [Buzzer] this will allow selection of [Disable], [Fault], [Fire] or
[Supervis] and then select [On/Off] and [Enter].
"
There is no indication given at the panel of buzzer disablement.

Software version check

The software version of the panel can be displayed by viewing the status of the master control
board / Main control card.
To check the software version of the Master control board / Main control card: Press Menu On/Off
button and then select [Info], momentarily press <etc> to select [Status] -> [Card] and enter Card
number 0, which is the Main control board / Master control card and then select [Enter]. The
display will show software version number and date of release.
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Vigilon 4/6 loops & Compact (VA) panels & network nodes

Password or PIN code

"
The terms Password, PIN (Personal Identification Number), Usercode and
Access code mean the same and are used interchangeably.
A password restricts access to the controls available to the user at the Control panel.
There are three access levels to the controls. These are access level 1, 2 and 3.
¨
The Access
level 1 controls only allow cycling through of multiple fire events
messages on the screen using the two buttons on the outer door.
¨
Access level 2a is for the CUSTOMER. Here the person responsible for the system
can access the 'essential controls' by opening the panel outer door using a key
¨
Access level 2b is for the CUSTOMER. Here the person responsible for the system
can access essential controls and some configuration menus using the panel door key
plus a customer PIN.
¨
Access level 3 is for the ENGINEER. Here the person responsible for the system can
access essential controls and all system menus using the panel door key plus Engineer
PIN.
¨
Daily PIN
There is another password that changes daily, which is available to the servicing
organisation. This daily password provides the same access to controls as the
Engineers' PIN. The daily PIN is only used when the Engineer's PIN is not known.
"
Always make a note of the Customer and Engineering PINs once they are
created. Ensure the Customer PIN is passed on to the person responsible for the fire
alarm system on the site.