Data and Installation
Connection diagram
&
The loop cable screen must be continued
through each interface module.
If a module is mounted on a DIN rail, then the DIN
rail must be electrically connected to the loop cable
screen.
Earth
Loop 0V
Loop L2+
Earth
Loop 0V
Loop L1+
"
The output contacts are rated at 13A 230V ac
resistive load. In order to meet the requirements of
European Safety Standards, ensure that all cables
carrying voltages in excess of 48V (Live and Neutral) are
suitably fused.
Dimensions
125mm
Depth 48mm
PCB on DIN rail
mountable module
At the end of their useful life, the packaging,
product and batteries should be disposed of
via a suitable recycling centre and in
accordance with national or local legislation.
WEEE Directive:
At the end of their useful life, the packaging,
product and batteries should be
disposed of via a suitable recycling centre.
Do not dispose of with your normal household waste.
Do not burn.
Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without
obligation to notify any person of such revisions of changes.
Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK
by Honeywell
Telephone: +44 (0) 116 246 2000
2
OUTPUT
NC
COM
NO
202mm
Depth 50mm
PCB in metal box
Interface (MV) - Output
Technical data
Approval
EN54-17:2005 & EN54-18:2005
(Pending Approval)
Dimensions
See illustrations
Weight
DIN mountable:138g
PCB with cover in metal box:800g
Storage
-30ºC to 70ºC
temperature
Operating
-10ºC to 60ºC
temperature
Relative
Up to 95% - Temperature
Humidity
5ºC to 45°C(Non condensing)
Emission
BS EN 61000-6-3:2001
Residential, Commercial & Light
Industry Class B limits
Immunity
BS EN50130-4: 1996: Part 4
LVD
BS EN 60950-2002
Ingress
Metal box - IP40 estimated
Protection
Colour -
Dark Grey
Metal Box
Output
Single pole change over contacts
rated at 13A 230V ac Resistive
load.
Contact ratings
1hp @ 240V ac, 1/2hp @
Type
120V ac (UL508)
3
Cycle
6x10
Terminals
2.5mm
Load Factor
5
(maximum 200 devices per loop)
EN54-17 data
V
max
V
nom
V
min
V
SO max
V
SO min
I
C max
I
S max
I
L max
Z
C max
Panel
Compatible with
compatibility
LPC = V3.92 / V4.33 &
MCC = V3.90 / V4.31.
4188-874.01_08/06_S4 MV O-P Interfaces
2
42V
40V
24V
14V
10V
0.4A
1A
20mA
0.1W
Website: www.gent.co.uk