Generic Commissioning instructions
Checking device status
To list the status of a device on an allocated loop at the Control
Panel: Press Menu On/Off button and then select [Info],
momentarily press <etc> to select [Status] -> [Device], enter a
device number, select [Loop], enter the loop number n, select
[Enter] to view device status information.
Description of
monitored input/LED
attached to the device
Loop on which
the device is installed
Loop 1 No.
7 Dual optical/Heat/CO
LED)
Loop breaker
LB1:C
End1:Hi
condition
I/O:...0 Anal:1-4
C:closed
2nd:250 3rd:0 Short delay:0
Zone 1
Zone 1
Tertiary address
used primarily by
sounders/strobe
Zone number and label
Secondary address
denotes group of devices
Digital
Input outputs
0 - Output, I - Input and . signifies not used
Device
digital I / 0
S cubed
0 0 0 0
1- IR control
2 - Tone
3 - Power
4 - Strobe
Sounder
. 0 0 .
3 - Low freq.
2 - On/Off
Repeat sounder
. 0 0 .
Interface unit (mains
all possible
powered)
I - input
0 - output
Optical
. . . 0
Optical heat
. . . 0
Heat
. . . 0
Slave Relay
0 . . 0+R
Slave LED
. . . 0 +L
Beam transmitter
. . . 0
Beam receiver
. . . 0
MCP
. . . 0
Repeat panel
. . . 0
Zonal mimic
. . . 0
50
Status of End 1
of the device
(high or low)
Location of the
device on the loop
Status of End 2
of the device
(high or low)
Device description
End2:Hi
,6
Short circuit delay
associated with
number of T breakers
off T breakers
Analogue channels
used
1:Optical (forward)
2:Heat
3:Gas
4:Optical (Backward)
5:Sounder/Strobe/Speech fault
6:Monitored line or LED
channels
5
1-channel 1
2-channel 2
3-channel 3
4-channel 4
5-battery
6-mains
1
1,2
4
2
1- raw data
2- average
data
6
-
-
Device
digital I / 0
Mimic panel
. . . 0
(standard A2 and A4
size)
Loop interface
all possible
I - input
0 - output
Single channel
I 0 . 0
interface unit
Loop powered zone
I . . 0
module
Optical/Heat
. 0 0 0
Sounder
T-breaker O/S
. . . 0
S-Quads
S-Quad Heat Sensor . . . 0
S-Quad Heat Sensor
. 0 0 0
Sounder
S-Quad Dual Optical
. . . 0
Heat Sensor
S-Quad Dual Optical
0 . . 0
Heat Sensor Strobe
S-Quad Dual Optical
. 0 0 0
Heat Sensor
Sounder
S-Quad Dual Optical
0 0 0 0
Heat Sensor Speech
Strobe
S-Quad Dual Optical
. . . 0
Heat Sensor CO
S-Quad Dual Optical
0 0 0 0
Heat Sensor CO
Speech Strobe
+ Monitored input
+ Monitored output
Analogue Channel 1 is forward scatter optical smoke sensor
Analogue Channel 2 is heat sensor
Analogue Channel 3 is for CO gas sensor
Analogue Channel 4 is for backward scatter optical smoke
sensor
Analogue Channel 5 reports sounder/flasher/speech faults to
the control panel
Analogue Channel 6 reports monitored input/monitored output
faults/operation to the control panel
"
The correct device type may not be displayed
if the loop circuit has allocation faults.
¨
Check that the device is of the correct type and is
suitable for the area in which it is installed.
¨
Check the digital status of all devices.
¨
On successful allocation
devices found equals the number
will be a loop voltage on the unconnected end of the
cable.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
channels
-
1-channel 1
2-channel 2
3-channel 3
4-channel 4
5
1,2,5
1,5
1,2
2
2, 5
1, 2,4
1, 2, 4, 5
1, 2, 4, 5
1, 2, 4, 5
1, 2, 3, 4, 5
1, 2, 3, 4, 5
6
6
check that the total number of
installed. Also there