Interface and panel outstations
Keyswitch
application
Line module
IO line test
NOTE: The supervisory mode is a non fire input used to trigger a
command build.
NOTE: On changing the setting of switches S1 and S2 the loop must be
reallocated.
q Where keyswitches are being used, they must be connected to
connectors P1 (for channel 1), P2 (for channel 2), P3 (for channel 3)
and P4 (for channel 4).
q Fit the keyswitch door to the interface unit. The door can accommodate
4 off 2-way keyswitches or 2 off 3-way keyswitches, see keyswitch
door option.
NOTE: A line module must not be used on a channel that has a
keyswitch connected to connectors P1, P2, P3 and P4.
q For keyswitch input, the interface board dual-in-line switches S1/S2
must be set to a normally open input.
q If a line module is used, set its switch S1 to the same, input or output,
setting as the interface channel to which it is connected.
q The line module may be installed in a remote location up to 100m cable
distance away.
NOTE: A maximum of 1Km cable usage per loop is allowed for the
connection of line modules installed in remote locations and 19245-06
power supply input output lines.
q Test the IO line as per project specification. The tests should be based
on the type of equipment interfaced, for example equipment such as air
conditioning system, escalator, fire door release or sprinkler system.
VIG-INT-LOOP - Loop powered interface
Vigilon Sys tem Com mis sioning