Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 15

For the fire alarm systems
Table of Contents

Advertisement

Applicable for Vigilon Compact VA panel only
n
(green)
All Zones
(green)
Clear Zones
Speak Now
(red)
Speak Now
(red)
Auxiliary messages
n
(red)
Emergency messages
n
(red)
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Voice Alarm Zones
1
2
6
7
All Zones
Auxiliary messages
1
TEST START
TEST END
2
STAND DOWN
3
Pressing one or more of the 10 buttons selects the Voice Alarm Zone to which emergency
or auxiliary messages, or emergency microphone is to be announced. The two LEDs
beneath flash alternately to show the Voice Alarm Zone has been selected.
On selecting the required emergency or auxiliary message only one of these LEDs
change to steady or flashing indication determined by the type of audio to be outputted to
the selected Voice Alarm Zones. The left LED indicates auxiliary message selection
while the right LED indicates emergency message selection.
Pressing the All Zones button allows quick selection of all Voice Alarm Zones. The
accompanying LED gives a steady indication when the button is pressed.
Pressing Clear Zones button will clear selected Voice Alarm Zones, also when auxiliary
messages are being announced pressing this button will silence the announcements.
When illuminated the system is ready to allow live speech announcement to selected
Voice Alarm Zones via the Emergency microphone.
The indicators are lit following selection of Voice Alarm Zones and on pressing the Press
to Talk (PTT) button on the Emergency microphone.
If the Press to Talk button is released the Speak Now indicators will flash and switch off
after 20seconds duration or immediately switch off on pressing the Clear Zone button.
When illuminated the system is announcing auxiliary message n to the selected Voice
Alarm Zones.
The indicator is lit following selection of Voice Alarm Zones and on pressing the
required Auxiliary message button.
When illuminated the system is announcing emergency message n to the selected Voice
Alarm Zones.
The indicator is steady or flashing determined by type of emergency message being
announced to Voice Alarm Zones.
Vigilon (EN & BS) Compact (VA) panels
3
4
5
8
9
10
Clear Zones
Speak Now
Emergency messages
1
ALERT
EVACUATE
2
BOMB
3
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gent viglion compact voice alarmGent viglion compactGent viglion bs

Table of Contents