Powering-up the Network

¨
Add one panel at a time starting from the network controller (the panel) at side 1.
"
It can take a few minutes for the system map to update.
¨
For each panel powered-up the network controller will automatically try to establish communication with the
connected equipment.
¨
The network controller will display the status of the network as being started, secure or non-secure and from now on
will monitor and control the network communications.
¨
Use disable comms to isolate a panel from the rest of the network, ie it operates at the network card in an echo
mode, select Menu On/Off -> [Control] -> [Disable] -> [Comms] and enter the Network Card usually card 6.

How to check a Network map

¨
Using the Menu On/Off -> [Info] -> [Map] -> [NetMap] menu, enter the network card address, usually 6.
The display will provide a list in cabling order the addresses of panels in the networked system.
¨
These are examples of different networks. The lowest address '1' is normally the network controller.
Nodes on side 1 of a SECURE NETWORK
1
10
Nodes on side 1 of a NON-SECURE NETWORK
1
10
Nodes on side 2 of non-secure network
1
23

How to check Network Card status

Using the Menu On/Off -> [Info] -> [Status] -> [Card] and enter the network card address. The display will confirm:
¨
address of the network card
¨
address of network controller
¨
and a set of condition codes
Card 6
Network (0) Version 4.xx
Address 5 Controller 5 Baud Rate 38400
condition 0 0 0 0 0 0 2 1 198 199
Side 2
Side 1
Parity/
Parity/
Framing
Framing
error
error
1 error = count of
10 but every 1sec
the counter is
decremented by 1
72
4
24
3
6
4
24
3
6
7
22
2
Is OK Fault 0: Warning 0
Side 2
Side 1
Side 2
CRC
CRC
Current
message
errors
1 error =
count of
100
2
22
7
23
30/04/04
Side 1
UART
type
communicating
0-Rckwell
Timing
1-Phillips
errors
2-Phillips SMT
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
1
Freeblock
End
1 or 2
Check
software
Only appears
on Controller

Advertisement