Generic Commissioning instructions

Manual Call Points

¨
Each call point should be tested for correct initiation of
a fire event.

Interface Units

&
1. In some instances it may not be possible to
functionally test input / output circuits off an
interface unit, such as when it is connected to plant
equipment.
2. Ensure the contact rating of interface output
circuits are adequate for the ancillary equipment
load requirement.
3. Fit a mains voltage warning label where mains
supply is being switched.
Ancillary equipment
¨
Tests should be carried out following customer
consent. It may also be necessary to obtain third party
consent.
¨
All tests on ancillary equipment should have been
agreed during the project design stage.
"
The loop powered single channel interface
output is not fault monitored, in this case the output tests
are not applicable.
Tests
¨
Each interface should be tested for the following:
Battery disconnection*
Mains supply disconnection*
Input line open circuit
Input line short circuit
Input line detector fire*
Input line MCP fire*#
Output line open circuit ~
Output line short circuit ~
Output line operation ~
* - not applicable for the loop powered interface units, but input
tests are applicable to loop powered zone module.
# - a fire from a manual call point or detector connected to a
loop powered zone module input cannot be differentiated.
~ - the output of the single channel interface operates with
sector. The output is a set of voltage free contacts which are
not fault monitored.
Interfaced equipment test
¨
The external equipment connected to the system via an
interface unit should be tested as per project
specification.
64
Keyswitches
¨
Where the interface unit has a keyswitch door fitted,
then the keyswitches should be configured for correct
operation and tested as per project specification.
¨
Check on operating the keyswitch the adjacent LED
will be lit.

S Cubed

"
The remote control is only operable when the
panel is in the zone Test mode (EN) / Commission mode
(BS).
Wall
3
S unit
Thinned
section
Remote Control
on base
Red LED
Off
Flash
Steady On
+
-
Perform a short press on the
the remote control. The Red LED will flash
x1 every 2 seconds
Press the
function button to toggle between:
Volume function and note the Red LED flashes
Tone
function and note the Red LED flashes
+
Press the
button to increase
-
Press the
button to decrease
3
Note: The strobe light on the S unit if fitted will flash rapidly when the volume is being
adjusted using the remote control.
Press and hold the
Power button to save the settings and adjustments.
The Red LED will remain On
whilst the button is held pressed.
The data is saved to the unit when the tone/speech on the S unit
stops briefly. Release the button on the remote control and the
Red LED will switch Off
.
¨
Depending on the type of S cubed device being
commissioned check to ensure correct output sound
tone, speech message and strobe rate are given. The
S-Cubed devices should have been setup using the
commissioning tool.
¨
The volume of the sounder S-Cubed device can be
adjusted by using a remote control.
¨
Each S-Cubed should be tested, for correct operation in
the event of fire.
¨
The sound levels in the areas should be tested in
accordance with the British Standard requirements and
to meet the site specific needs as agreed with the
customer.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Trouble shooting
If the remote control fails to operate in close
3
proximity to the thinned section of the S
product, then a possible cause may be the
battery. Replace the battery.
Power button to turn On
x1 every 2 seconds
x2 every 2 seconds
volume
or to select the next
tone
volume
or to select the previous
tone
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gent viglion compact voice alarmGent viglion compactGent viglion bs

Table of Contents