Checking A Loop Map; To Find Devices On Loop Circuit - Honeywell Gent Viglion EN54 Generic Commissioning Instructions

For the fire alarm systems
Table of Contents

Advertisement

Checking a loop map

A loop map is checked against the as fitted wiring drawings. This
will confirm the exact location of each system device and its
address.
¨
It is possible to display or print a loop map. The
following procedure assumes no password access is
required. Press the Menu On/Off button and then
[Info] -> [Display]/[Print] note these options will only
appear if a printer is connected to the panel.
Momentarily press <etc> to select [Loop Map], type
in a loop number and select [Enter]. The loop map is
either displayed or printed. A typical example is
shown:
Map information for Loop 2
Os Prev Next
Common
1
End1
2
2
1
3
3
2
4
4
3
9
L2
5
4
6
6
5
7
7
6
8

To find devices on loop circuit

¨
Checking physical location of devices on a loop map is
made easier by having two people in communication
with each other. While one person walks around the
site and marks the devices on the as fitted wiring
drawings, the other person operates the panel controls.
¨
The find device is a function that gives visual or
audible indication at the respective device on a loop
circuit.
The following procedure assumes no password access
is required.
Press the Menu On/Off button and then [Test/Eng]
->[Loop] ->[Find Dev], now enter CARD number n to
select the loop circuit n, select [Start] and type in a
device number (usually device 1) and select [Enter].
The display shows the device and loop number:
Number 1 on Loop 1
¨
Press [Next] to find the next device on the loop and at
any stage if the previous device needs to be found then
select [Previous].
¨
A found device will provide visual or audible
indication.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
15:45
Position
Main Loop
Main Loop
Main Loop
5
Spur Loop
Spur Loop
Spur Loop
Spur Loop
Spur Loop
Vigilon (EN & BS) Compact (VA) panels
Sensors and MCP
¨
A fire sensor or system manual call point will operate
its LED for 0.5 second On and 0.5 second Off repeated.
Sounders and S cubed
¨
Each system alarm sounder or S cubed or S-Quad
device will provide an audible and / or visual
indication for 0.5 second On and 0.5 second Off
repeated.
Interface units
&
Ensure outputs are not connected to
external equipment at this stage of commissioning.
¨
Each interface output will in turn be activated for 0.5
second On and 0.5 second Off , this will repeat.
"
The loop powered zone module and single
channel interface will provide an indication by switching
on the red LED (D22) on the interface board.
Panels on loop circuits
¨
A mimic and repeat panel on a loop circuit will
display its device number.
¨
Check the suitability of each device for the area in
which it is installed and the location of installation with
reference to the as fitted drawings.