Sectors - Honeywell Gent Viglion EN54 Generic Commissioning Instructions

For the fire alarm systems
Table of Contents

Advertisement

Sectors

*
I/O LINES MAY BE SECTORED INDIVIDUALLY
ONLY FOR STANDARD MAINS POWERED INTERFACE UNITS
AND NOT FOR LOOP POWERED INTERFACE UNITS
DEVICES
ASSIGN
& I/O LINES
WITHIN A
*
SECTOR
DELAY
ACTION
BLOCK
COMMAND
ACTION
BUILD
SECTOR
ACTION
That has just
come into fire
¨
There can be up to 32 sectors per loop
¨
a sector is a collection of devices on the same loop having a common action.
¨
a sector that is actioned ON will activate its alarm devices, such as interface outputs, S cubed and alarm sounders.
¨
a sector can be configured to give one of three signals
Signal 1 Alert (priority 3)
Signal 2 Evacuate (priority 2)
Signal 3 Continuous (priority 1)
¨
sectors 1-28 operate automatically with 'Sound Alarms' and 'Silence Alarms' buttons
¨
a sector (any one of 1-28) that is configured for NO action on 'Sound Alarms' button will be silenced on operation
of the 'Reset' button
¨
the sectors 29-32 are independent of the 'Sound Alarms' button and are primarily used with Fixed Extinguishant
interface product which is not no longer supported. However the sectors 29-30 can be configured to normal sector
operation.
¨
sensors, call points and interface inputs may be assigned to more than one sector.
¨
a loop powered interface is assigned to a sector and consequently the inputs and outputs lines of
be assigned to the same sector.
¨
alarm sounders, OHS and interface outputs are restricted to one sector only.
¨
There can be up to 10 Voice Alarm Zones.
¨
Voice alarm zone are push button switches on the control panel that can be assigned to Sectors.
¨
Any normal Sector (1-28) can be assigned to any voice alarm zone (1-10)
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
SIGNAL
1
SIGNAL
2
SIGNAL
3
SIGNAL
1
ALL
SIGNALS
OFF
SIGNAL
2
SIGNAL
3
SIGNAL
1
ALL
SIGNALS
SIGNAL
OFF
2
SIGNAL
3
ALL
SIGNALS
OFF
DEFAULT: SIGNAL-1 = ALERT
SIGNAL-2 = EVACUATE
SIGNAL-3 = CONTINUAL
Vigilon (EN & BS) Compact (VA) panels
SECTOR FUNCTIONS
32 SECTORS
PER LOOP
TRIGGER
NOTE : SECTORS 29 TO
32 ARE FOR
ACTION
SPECIAL USE
ACTION
SECTOR
ACTION
SETUP THE SECTOR
TO DE-ENERGIZE ON
ASSIGN
SILENCE ALARMS
OR RESET
BUTTON
ASSIGN
NOTE : A SECTOR CAN ONLY ACTION OTHER LINKS
IF THE FIRE IS AT A DEVICE ASSIGNED TO THAT SECTOR.
NOTE: Voice alarm zones are push button
controls on the main panel.
COMMAND
BUILD
DELAY
BLOCK
AUX
RELAYS
SECTOR
VOICE ALARM
ZONES
MASTER
SECTOR
that interface will
117