Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 180

For the fire alarm systems
Table of Contents

Advertisement

In ter face and panel out sta tions
VIG-MIM/ZONE Mimic or Zonal panel
Zonal panel
Mimic panel
Figure 3-1 Mimic panel
battery connection
cd8m087
See also Mimic configurer part of this manual.
q Unhook the front cover.
NOTE: The zonal panel is supplied with the pre-programmed EPROM and
the zone designation plan fitted.
q A custom site plan must be fitted in-between the two translucent sheets
of the panel front cover. Also a custom EPROM must be fitted on the
master repeat card, see Mimic configurer part of this manual.
NOTE: Ensure the custom site plan is fitted to the panel to coincide with
the LED matrix.
q Open the hinged inner door.
q Connect the mains supply and power-up the panel.
• the green and amber LEDs on the master repeat card are lit
• the local buzzer sounds for a short duration
• after a short duration a message will appear on the mimic panel:
OFF LINE
q Operate the keyswitch on the panel, this will:
• cancel the local buzzer
• and carry out lamp test.
q Connect the battery supply.
VIG-MIM/ZONE Mimic or Zonal panel
Vigilon Sys tem Com mis sioning