Heat Sensor States (34000 Range); Beam Sensor States (34000 Range) - Honeywell Gent Viglion EN54 Generic Commissioning Instructions

For the fire alarm systems
Table of Contents

Advertisement

Heat sensor states (34000 range)

State
Definition
State 0
(Default) Grade 2, rate of rise and
fixed temperature
(LPC
approved)
State 1
Grade 1, faster rate of temperature
(LPC
rise as well as fixed temperature
approved)
State 2
Grade 1, limited rate of rise
State 5
High temperature with rate of rise
State 6
High temperature with no rate of
rise
State 15
No detection

Beam sensor states (34000 range)

Beam sensor
Path length
Short path
2-30m
Long path
from 30-100m
State
Definition
State 0
Default detection
(LPC
approved
)
State 1
Normal sensitivity
State 2
Medium Sensitivity
(LPC
approved)
Medium Sensitivity
State 3
State 4
High Sensitivity
State 5
High Sensitivity
State 15
No detection.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Vigilon (EN & BS) Compact (VA) panels
Application
Suitable for general use in ambient temperatures up
o
to 40
C. Provides detection to Grade 2 performance
as defined in BS5445 : Part 5.
Applicable for areas with normally very steady low
ambient temperatures. A faster rate of rise can
signal a fire below the normal set temperature at
o
58
C.
Applicable for normal ambient temperature where
temperature variations are expected up to 40
faster response than grade 2 is required e.g. hotel
bedroom.
Provides detection as specified by Range 1
BS5445:Part 8 .
Provides detection as specified by Range 1
BS5445:Part 8.
No detection. This is a total disablement of the
sensor.
State
State 2/3
State 0/1
Application
A fire is detected when there is a 50% (3dB) fall in signal level,
however if the fall is by 90% (10dB) in less than 1second and is
maintained for 40 seconds, then a fault is registered. This allows
the Control panel to differentiate between a fire and a fault signal
caused by accidental obscuration.
A fire is detected when there is a 50% (3dB) fall in signal level,
however if the fall is by 90% (10dB) in less than 1 second and is
maintained for 40 seconds then a fire is registered.
A fire is detected when there is a 25% (1.3dB) fall in signal level,
however if the fall is by 90% (10dB) in less than 1 second and is
maintained for 40 seconds then a fault is registered.
A fire is detected when there is a 25% (1.3dB) fall in signal level,
however if the fall is by 90% (10dB) in less than 1 second and is
maintained for 40 seconds then a fire is registered.
A fire is detected when there is a 10% (0.5dB) fall in signal level,
however if the fall is by 90% (10dB) in less than 1 second and is
maintained for 40 seconds then a fault is registered.
A fire is detected when there is a 10% (0.5dB) fall in signal level,
however if the fall is by 90% (10dB) in less than 1 second and is
maintained for 40 seconds then a fire is also registered.
This is a total disablement of the sensor.
o
C but
59