Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 106

For the fire alarm systems
Table of Contents

Advertisement

Generic Commissioning instructions
Message
Loop map has
changed card x
Loop power
restored
Loop Started not
ready at card x
number y loop z
Loop stopped at
Card x
Loop voltage too
high/low
Lost Command
number x on
Loop y
Lost Device
number x on loop
y
Lost slave
Device number x
on loop y
Magnetic switch
operated
number x loop y
Main program not
running at
card x
Mains failed /
restored
Mains too high
Mains too low
Master alarm
oc
or
sc
Restored
106
associated with..
meaning..
Loop Processor
The map is different to that
Card
previously allocated.
Power supply
Normal loop supply
restored:
Normal ADC = 202 (44V).
Value = Vsupp x
1/11X256/5.
Loop Processor
As per message.
Card
Loop Processor
The loop has been aborted
Card
or is still being allocated.
Power supply
The ADC value too high.
or
The ADC value is too low.
Loop Processor
Lost FAB/SAB.
Card
Loop Processor
There is no reply on ends
Card
1&2 of the device.
Loop Processor
There is no reply on ends
Card
1&2 of the device.
Device
The reset switch in the base
has closed.
Any Card
Problem with software. The
watchdog will operate the
MCC / MCB (main control
card/board).
Power supply
Failure is detected when
the ADC output from the
rectifier is equal to or less
than 105.
Power supply
The ADC value is too high.
Power supply
Mains supply is too low.
Power supply
No end-of-line unit seen.
ADC value is greater than
92
or
ADC value is less than 37
ADC value is 74
..possible action
Check and confirm difference
with backup map.
-
Wait and if it takes longer
than
10 minutes then reset the loop
card.
Re-allocate the loop.
Check PSU values in the
[Test/Eng] menu, normal
reading is 221. Replace PSU
if necessary.
Ignore single occurrence and
record in log book.
Check the device
connections.
Check the slave device
connections and replace if
necessary.
Check base and proximity of
magnetic field.
Software errors will activate
a system reset.
Ignore single occurrence.
Record event in log book.
Check mains and fuse.
Replace PSU if necessary.
This should normally equal to
60V to get a restored
message.
Check the PSU values in the
[Test Eng] menu. Replace
PSU if necessary.
Check the wiring to the
master alarm circuits. Ensure
EOL is connected inside the
control panel if master alarm
circuits are not used.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.