Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 107

For the fire alarm systems
Table of Contents

Advertisement

Message
Master alarm
enabled/disabled
Master alarm
restored
Master
polling/not
polling at
card x
Master Sector
Actioned
Master Sector
Enabled/Disabled
Memory corrupt
number x loop y
Message
discarded
Neighbour ACK
Failed at card n
Neighbour ACK
Invalid at
card n
Network
initialised at
Card x
Network Insecure
/ Secure at
Card x
Network starting
at Card x
Network wiring
fault at card x
New address n at
card x
New domain
address n at
Card x
NMI's missed at
card x
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
associated with..
meaning..
MCC / MCB (main
The master alarm has been
control card/board)
enabled or disabled
automatically or manually.
Power supply
Master alarm fault cleared.
The ADC value should be
74.
MCC / MCB
PC or SRI (service request
interface) is not
handshaking with the
control panel
MCC / MCB (main
Master sector has been
control card/board)
switched ON/OFF.
MCC / MCB (main
Master sector has been
control card/board)
enabled or disabled
manually or automatically.
Device
FLASH checksum failure
TBA
TBA
-
Repeated address
TBA
TBA
Network Card
Successful network map
with polled panels.
Network Card
There are 3 missing replies
in a row on End-2 of the
controller.
Network Card
Communication starting
with other connected
panels.
Network Card
Wiring is presumed to be
oc between
panel n and panel n.
MCC / MCB
The new address set has
Network Card
been read.
Network Card
The new address set been
read at the particular card.
Loop Processor
Software error.
Card
Vigilon (EN & BS) Compact (VA) panels
..possible action
If necessary, manually enable
or disable the master alarm
using the [Control] menu.
Check the wiring
-
If necessary manually enable
or disable the master sector.
Replace the device
TBA
Check domain addresses are
unique
TBA
-
Check the wiring.
Check the error rate.
-
Check the wiring.
-
-
Software errors will activate
a system reset.
Ignore single occurrence.
Record the event in log
book.
107