Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 110

For the fire alarm systems
Table of Contents

Advertisement

Generic Commissioning instructions
Message
SAFE Address not
Set up number x
on loop y
Scan error
number x at
card y
Sector actioned
Sector Enabled/
Disabled at card
x
Sensor out of
specification
number x on Loop
y Channel z
Shared memory
hardware is
faulty at Card x
Slave Device
Replaced
number x on loop
y
Slave micro
failed at Card x
Software errors
Sounder circuit
failed
Sounder circuit
Restored
Speech circuit
has failed
Speech circuit
Restored
110
associated with..
meaning..
Loop Processor Card
The replaced device is not
SAFE addressed. The
device previously installed
in the location was SAFE
addressed.
Loop Processor
Invalid universal scan
Card
reply.
Loop Processor
Sector is switched
Card
ON/OFF.
Loop Processor
The sector(s) has been
Card
enabled or disabled
automatically or manually.
Loop Processor
Fault pattern has been
Card
matched.
Any Card
There is MCC / MCB
problem.
Loop Processor
Slave type device has been
Card
replaced.
Loop Processor
Loop driver is
Card
watchdogged by loop
processor.
Software errors will
Software error
activate a system
reset
Device
There is a fault with the
sounder hardware on the
S-cubed or S-Quad.
Device
The fault on the sounder
circuit associated with
S-Quad or S-Cubed has
been restored.
Device
There is a hardware fault
possibly associated with
the voice chip on the
speech S-cubed or S-Quad
Device
The fault on the speech
S-Quad and S-Cubed has
been restored.
..possible action
Set up the SAFE address.
Check loop length and
screening
-
If necessary , manually
enable/disable the sector
using the [Control] menu.
Check and replace the sensor
if necessary.
Replace all other cards than
the MCC/MCB. See if the
problems persists.
Replace MCC / MCB if
necessary.
-
Reset and ignore single
occurrence. Record in log
book.
Software errors will activate
a system reset.
Ignore single occurrence.
Record the event in log
book.
Replace the device
-
Replace the device
-