Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 111

For the fire alarm systems
Table of Contents

Advertisement

Message
Spurious
acknowledgment
at card x
Spurious FAB
Number x on Loop
y
Stack overflow
at card x
Stack too deep
at card x
Strobe circuit
has failed
Strobe circuit
restored
Sub Faults
Superfire number
x on loop y
channel z
Supply totally
Failed
Switching
inhibited at
end 1 at card x
System Printer
fitted at card x
number y loop z
System Printer
Lost at card x
number y on
loop z
System Restarted
/Started
System stopped
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
associated with..
meaning..
Any Card
Software error.
Loop Processor
Device has FAB but
Card
shouldn't have any.
Any Card
Software error
Any Card
Software error.
Device
The strobe circuit on the
S-Quad or S-Cubed device
has failed.
Device
The strobe hardware fault,
such as internal connection,
on the S-cubed or S-Quad
has been restored
Loop Processor
Pattern match is equal to or
Card
greater than a Fire.
MCC / MCB (main
The message does not
control card/board)
normally appear.
Network
Automatic end swapping
on the network controller
has been disabled for test
purpose.
MCC / MCB (main
An 80 column serial printer
control card/board)
is fitted to the panel.
MCC / MCB (Printer
TBA
option)
MCC / MCB (main
Link on back plane
control card/board)
restored.
MCC / MCB (main
Backplane link moved
control card/board)
causing the system to stop.
Vigilon (EN & BS) Compact (VA) panels
..possible action
Software errors will activate
a system reset.
Ignore single occurrence.
Record the event in log
book.
Ignore single occurrence.
Panel will remove the
indication.
Software errors will activate
a system reset
Ignore single occurrence.
Record the event in log book
Software errors will activate
a system reset.
Ignore single occurrence.
Record the event in log
book.
Replace the device
-
See exceptions
-
-
-
-
TBA
-
The link should not be
normally accessed.
111

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gent viglion compact voice alarmGent viglion compactGent viglion bs

Table of Contents