Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 112

For the fire alarm systems
Table of Contents

Advertisement

Generic Commissioning instructions
Message
Task stuck
at
card x
Test set found /
removed at
Card x
Too many errors
number x on loop
y
Too many errors
x at Card y
Two controller
at Card x
Two master has
the same address
at
Card x
Unable to claim
buffers at
card x
Unrecoverable Tx
fault
number x loop y
Warm restart
Warning cleared
Wiring changed -
ground break at
card x number y
on loop z
Wiring changed -
short at
card x number y
loop z
Wiring changed -
split/closed at
Card x number y
on loop z
Wiring changed
part short at
Card x number y
on loop z
112
associated with..
meaning..
Any Card
Software error.
Loop Processor
Remote allocation unit has
Card
been found connected to
the system.
Device
More than 15 errors from a
device in 34 hours.
Network Card
Up to 6 consecutive
communication errors.
Network
There are two network
controllers.
MCC / MCB / DKC
Two PCs have been given
the same address.
Any Card
System too busy
Loop Processor
More than 3 consecutive
Card
reply errors
MCC (main control
The 5V rail has seen a dip
card)
activating the watchdog or
the button has been pressed
on MCC/MCB or panel
power reconnected.
MCC / MCB (main
Warning has been
control card/board)
removed.
Loop Processor
A test has shown a break
Card
on the 0V line. The test is
conducted every minute.
Loop Processor
Loop short circuit after the
Card
particular device.
Loop Processor
No reply received from a
Card
device at End-2 of loop.
Loop Processor
Less than 80 ohms between
Card
the +ve and 0V of loop
wiring.
..possible action
Software errors will activate
a system reset.
Ignore single occurrence.
Record the event in log
book.
Disconnection of the test set
will bring about a removed
message.
Check the loop wiring to the
device.
Check wiring and cable
screen. There may be faults
with the installation.
One network controller will
automatically shut down.
Each PC must have a unique
address.
Wait or reset card if stuck,
record in log book
Check the device connections
and replace if necessary.
-
-
Check wiring of 0V around
loop.
Check wiring and device
after indicated device.
Check wiring, there can be
other reasons.
Check wiring and device
after the partially shorted
device.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.