Address allocation

&
Always power-up with the mains supply
first and then connect the battery. The power-down
sequence should be in the reverse order.
Main
loop
circuit
END 1
Previous
Next
CONTROL PANEL

Connecting Loop 1 circuit

&
Ensure the panel is powered down first
before connecting the external loop cables to the
panel.
It is recommended that each external circuit is wired up to the
terminals at the panel, one circuit at a time and tests conducted
to ensure that each circuit is functioning correctly. We start by
connecting End 1 only.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
1
2
3
31
30
Spur
on
main
29
loop
Spur
main
loop
28
32
27
26
Note: The End 2 connection is
not made at this stage of commissioning
Vigilon (EN & BS) Compact (VA) panels
9
10
4
Spur on main loop
5
6
7
23
24
22
on
21
20
19
18

With Loop 1 End 1 connected

¨
Ensure end-2 of the loop cable remains
disconnected.
¨
Connect the mains and battery supply to power up the
panel, you will initially see the powering up messages.
If there are no device address allocation faults the
panel will start the loop.
Allocating Loop n
Allocation: OK at Card X : Allocated Y
Starting Loop n
Loop started OK at Card X: Started Y
¨
Even if all the devices are wired correctly and there are
no allocation faults, there may still be some device
faults, like mains and battery disconnected at interface
units, these will be displayed at the panel. The panel
fault buzzer will sound and the Fault LED will be lit.
¨
To stop the local buzzer from sounding press
Cancel Buzzer button.
"
In practice there may be system wiring and
hardware faults during the address allocation stage,
these faults are also displayed as messages and for
further information on what they mean and possible
action that can be taken, see Appendix B - Message