Auxiliary Relays

The two auxiliary relays in the control panel are defaulted to
operate on a sectored fire event aux relay 1 and Fault event aux
relay 2.
¨
the auxiliary relays can be configured for
normally-open or normally-closed operation.
¨
the relays may be configured to be operated with:
a Fault
a Warning
any combination of Sectored Fire events
or any of the above combination
¨
It is possible to delay the operation of each relay by up
to 10 minutes after the first FIRE event. The accuracy
of the delay is 0 - 4 seconds.
¨
The relay will operate immediately for fault and
warning events.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Vigilon (EN & BS) Compact (VA) panels