Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 187

For the fire alarm systems
Table of Contents

Advertisement

Fine adjustment
Fine adjustment
Vigilon Sys tem Com mis sioning
g)
Unlock the lock nuts to allow Y axis adjustment and using the
adjusters move the transmitter head in a Y direction, then:
• stop on reaching a time average reading 5 bits below the peak
value
• while counting the number of turns, adjust in the opposite direction
to reach 5 bits below the peak value
• finally turn the adjuster half the number of counted turns, towards
the peak and then stop
• secure the axis adjusted using the lock nuts
h)
Repeat g) for adjustment in the X direction.
i)
Repeat g) and h) at the receiver head.
l)
Carry out a final [Autogain]. Then recheck the time average reading
is within 140 to 170 band.
m)
Back up the appropriate loop processor card LPC (which holds the
gain data) to the RAM using [Back Up] command in the [Set Up]
menu.
VIG-BEAM Beam sensor