Pointer missing
at card x
Prefire number x
on loop y
channel z
Printer
lost/fitted at
card x number y
on loop z
Program memory
corrupted at
card x
Program not
running at
Card x
Program runaway
at card x
Q buffer full at
card x
Q buffer number
Failed at card x
Recover failed
at Card x
Recover
succeeded at
card x
Replaced Device
Wrong type
number x on loop
y
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
associated with..
meaning..
Any Card
Software error
Loop Processor
Pattern match less than a
Card
Fire.
MCC / MCB / DKC
The external printer has not
/ MRC
been seen and is 'lost'.
Any Card
Checksum failure on
FLASH at midnight.
Any Card
Problem with software, the
watchdog will operate the
MCC / MCB (main control
card/board).
Any Card
CPU has crashed.
Any Card
Software error.
Any Card
Software error.
Loop Processor
Loop does not match what
Card
is on NVM card.
Loop Processor
Successful recovery after a
Card
previous failure.
Loop Processor
Device is a different type.
Card
Vigilon (EN & BS) Compact (VA) panels
..possible action
Software errors will cause a
system reset.
Card fault should be ignored
for single occurrence.
Record the event in log
book.
-
Check the connections to the
printer.
jam in the printer
Clear and ignore single
occurrence. Record in log
book.
Software errors will activate
an automatic system reset.
Ignore for single occurrence.
Record event in log book.
Clear and ignore single
occurrence. Record in log
book.
Software errors will activate
a system reset.
Ignore single occurrence.
Record the event in log
book.
Software errors will activate
a system reset.
Ignore single occurrence.
Record the event in log
book.
Check and confirm/correct
the difference and then
backup.
-
Check and confirm
installation of correct type
and reallocate. Back up to
memory.
Also check for paper
mechanism.