Non Volatile Memory
(NVM)
The Backplane and the Master Control board fitted inside
the panel have the Non Volatile Memory (NVM).
The NVM should the latest system configuration data.

Hardware write protect

&
Do not attempt to write protect using the
link P13 while a back up to the flash chip or
initialisation of the memory is in progress.
The link header P13 on the Backplane provides hardware write
protection and will stop [Save] and [Back-up] commands from
the panel controls modifying the memory. The link is factory fitted
to allow card data to be saved to the NVM.
"
Where the system is required to be EN54 Part 2
compliant, then the link P13 must be left in the protect
enable state, that is to disallow write to NVM.
Hardware write protect on Vigilon 4-loop
panel
Exisiting Vigilon 4-loops panel
Backplane
TERMINALS
FOR CARD IN P8
1 2 3 4 5 6 7 8
TERMINALS
FOR CARD IN LOOP 5
1 2 3 4 5 6
IC2
IC1
P13
P13
P13
Write protected
NOT Write protected
(factory setting)
Hardware write protect on Vigilon Compact
(+ VA) panels
Master Control Board
24V
0V
B A
NC C NO
NC C NO
NC C NO
0V TX A RX B
L1 0V L2 0V L1 0V L2 0V
P15
P10
P11
P6
P14
24V
FS3 200mA
P1
CARD 2
P2
CARD 1
BATT1
CODE
BCKUP
IC3
IC16
P16
P13
Non Volatile
Memory - NVM
There is also 'software'
NVM protect enable and
disable, see menu maps.
44
New Vigilon 4/6-loops panel
Backplane
P13
LK1
Protected
- Write protected
Unprotected
- NOT write protected
(factory setting)
NEW Master Control Board (MCB)
0V MIPNC C NO
24V
0V
B
A
L1 0V L2 0V
NC C NO NC C NO NC C NO
MA1+ MA1- MA2+ MA2-
TX1 RX1 0V
TX2 RX2
P7
P9 P8
PB15
PB6
PB14
PB10
MA2 - FS2 250mA
24V
FS3 200mA
MA1 - FS1 250mA
P1
CARD 2
FIRMWARE BACKUP
IC16
IC3
POWER
SUPPLY
P12
SW2
MODE
P16
SW1
'
Hardware' NVM protect link P13
Factory setting is NVM protect
disabled
NVM protect - [Disabled]
(ie NVM unprotected,
that is
write allowed
)
NVM protect - [Enabled]
(ie NVM protected,
that is
write not allowed
)

The configuration data held at the panel

Master Controller Card (MCC)
¨
Holds the status or configuration of:
printer state - On/ Off
usercode - the user entry password
timeslots and time blocks
sounder configuration for all three Signals plus IO
line
auxiliary relay
action/deaction #
assign/remove #
setup #
# - some exceptions are held on the loop processor
card
Loop Processor Card (LPC)
¨
Holds the status or configuration of devices:
labels
gain
assign/remove to sectors
setup of states and timeblocks.
L1 0V L2 0V
0V MIPNC C NO
MA1+ MA1- MA2+ MA2-
PB11
PB7
PB9
PB8
MA1 - FS1 250mA
MA2 - FS2 250mA
P2
CARD 1
POWER
SUPPLY
P12
SW1
BATT1
RESET
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.