Product Approval And Standards; Fire Detection And Alarm Control Panel; S-Quad Sensors - Honeywell Gent Viglion EN54 Generic Commissioning Instructions

For the fire alarm systems
Table of Contents

Advertisement

Product Approval and Standards

Fire detection and alarm control panel

The following fire detection and alarm control panels are LPCB approved.
Product number Description
VIGn
EN Vigilon 4 loop panels
n can be 1, 2, 3 or 4
The COMPACT_N, VIG1-24 and VIG1-72 panels described in this manual are pending approval.

S-Quad Sensors

The following S-Quad sensors when operating in the states shown in table below are LPCB approved to the respective standard.
Product number Description
S4-720
Heat sensor
S4-780
Heat Sensor Sounder
S4-711
Dual Optical Heat Sensor
S4-711-ST
Dual Optical Heat Sensor Strobe
(Strobe - no approval)
S4-911
Dual Optical, Heat & CO Sensor
(CO - no approval)
S4-711-ST-VO
Dual Optical Heat Sensor Speech strobe
(Speech and Strobe - no approval)
S4-771
Dual Optical Heat Sensor Sounder
S4-911-ST-VO
Dual Optical Heat CO Sensor Speech & Strobe
(Speech, Strobe & CO - no approval)
* - these devices are LPCB approved when operating in the LPCB approved STATE, see table below.
"
If an S-Quad sensor is configured to operate a non LPCB state, then this will contravene the LPCB approval.
The required state is configured during commissioning and can be configured at the control panel.
Dual optical & Heat sensor
(S4-711 & S4-711-ST)
Dual optical, Heat & CO sensor
(S4-911)
Heat sensor (S4-720)
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Approval
EN 54 Parts 2 & 4.
Device
LPCB approved
sensor STATE *
State 0
State 5
State 8
State 0
State 9
State 0
State 5
Vigilon (EN & BS) Compact (VA) panels
Standard
EN54 : Part 5 :2002* (heat)
EN54 : Part 5 :2002* (heat)
EN54 : Part 3 2001 - (sounder tone~)
EN54 : Part 7 :2000* (optical smoke)
EN54 : Part 5 :2000* (heat)
CEA 4021 : 2003-07 Class P heat multisensor detector
EN54 : Part 7 :2000* (optical smoke)
EN54 : Part 5 :2000* (heat)
CEA 4021 : 2003-07 Class P heat multisensor detector
EN54 : Part 7 :2000* (optical smoke)
EN54 : Part 5 :2000* (heat)
CEA 4021 : 2003-07 Class P heat multisensor detector
EN54 : Part 7 :2000* (optical smoke)
EN54 : Part 5 :2002* (heat)
EN54 : Part 3 2001 - (sounder tone~)
CEA 4021 : 2003-07 Class P heat multisensor detector
EN54 : Part 7 :2000* (optical smoke)
EN54 : Part 5 :2002* (heat)
EN54 : Part 3 2001 - (sounder tone~)
CEA 4021 : 2003-07 Class P heat multisensor detector
EN54 : Part 7 :2000* (optical smoke)
EN54 : Part 5 :2002* (heat)
EN54 : Part 3 2001 - (sounder tone~)
CEA 4021 : 2003-07 Class P heat multisensor detector
Meets
Medium optical smoke / Class A1 heat
Medium optical smoke / Class B heat
Delayed medium optical smoke / Class A1 heat
Medium optical smoke / Class A1 heat
Class A1 heat
Class A1 heat
Class B heat
9