Product Approval and Standards
Fire detection and alarm control panel
The following fire detection and alarm control panels are LPCB approved.
Product number Description
VIGn
EN Vigilon 4 loop panels
n can be 1, 2, 3 or 4
The COMPACT_N, VIG1-24 and VIG1-72 panels described in this manual are pending approval.
S-Quad Sensors
The following S-Quad sensors when operating in the states shown in table below are LPCB approved to the respective standard.
Product number Description
S4-720
Heat sensor
S4-780
Heat Sensor Sounder
S4-711
Dual Optical Heat Sensor
S4-711-ST
Dual Optical Heat Sensor Strobe
(Strobe - no approval)
S4-911
Dual Optical, Heat & CO Sensor
(CO - no approval)
S4-711-ST-VO
Dual Optical Heat Sensor Speech strobe
(Speech and Strobe - no approval)
S4-771
Dual Optical Heat Sensor Sounder
S4-911-ST-VO
Dual Optical Heat CO Sensor Speech & Strobe
(Speech, Strobe & CO - no approval)
* - these devices are LPCB approved when operating in the LPCB approved STATE, see table below.
"
If an S-Quad sensor is configured to operate a non LPCB state, then this will contravene the LPCB approval.
The required state is configured during commissioning and can be configured at the control panel.
Dual optical & Heat sensor
(S4-711 & S4-711-ST)
Dual optical, Heat & CO sensor
(S4-911)
Heat sensor (S4-720)
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Approval
EN 54 Parts 2 & 4.
Device
LPCB approved
sensor STATE *
State 0
State 5
State 8
State 0
State 9
State 0
State 5
Vigilon (EN & BS) Compact (VA) panels
Standard
EN54 : Part 5 :2002* (heat)
EN54 : Part 5 :2002* (heat)
EN54 : Part 3 2001 - (sounder tone~)
EN54 : Part 7 :2000* (optical smoke)
EN54 : Part 5 :2000* (heat)
CEA 4021 : 2003-07 Class P heat multisensor detector
EN54 : Part 7 :2000* (optical smoke)
EN54 : Part 5 :2000* (heat)
CEA 4021 : 2003-07 Class P heat multisensor detector
EN54 : Part 7 :2000* (optical smoke)
EN54 : Part 5 :2000* (heat)
CEA 4021 : 2003-07 Class P heat multisensor detector
EN54 : Part 7 :2000* (optical smoke)
EN54 : Part 5 :2002* (heat)
EN54 : Part 3 2001 - (sounder tone~)
CEA 4021 : 2003-07 Class P heat multisensor detector
EN54 : Part 7 :2000* (optical smoke)
EN54 : Part 5 :2002* (heat)
EN54 : Part 3 2001 - (sounder tone~)
CEA 4021 : 2003-07 Class P heat multisensor detector
EN54 : Part 7 :2000* (optical smoke)
EN54 : Part 5 :2002* (heat)
EN54 : Part 3 2001 - (sounder tone~)
CEA 4021 : 2003-07 Class P heat multisensor detector
Meets
Medium optical smoke / Class A1 heat
Medium optical smoke / Class B heat
Delayed medium optical smoke / Class A1 heat
Medium optical smoke / Class A1 heat
Class A1 heat
Class A1 heat
Class B heat
9