Battery connection

¨
Remove the lithium battery insulation sleeve or disk to
allow it to come in direct contact with retaining
connector.
BATT1
Remove Sleeve

Switching the essential controls

Factory set link position:
Control buttons active
Control buttons are active
Control buttons:
Sound alarms button
Silence alarms button
Reset button
Verify button
Control buttons are inactive
or
Looking on the inside of the inner
door
"
There is no indication given at the panel when
the links are set for inactive controls.

Factory settings

Ports
P0 - RS485, Baud: 1200 Mode: Repeat
P1 - RS232, Baud: 38400, Mode: Standard
P2 - RS232, Baud: 38400, Mode: Standard
P3 - USB
System configuration
Domain address - 0
Panel (Node) address - 1
All devices assigned to sector 1
All devices assigned to zone 1
28

Power up

Battery supply
¨
Fit the battery lead to the PSU.
Remove the battery bracket from the backbox.
Fit the batteries in the correct orientation.
Refit the battery bracket.
"
The panel makes use of sealed lead acid type
batteries which can have a useful life of up to 5 years
from the date of manufacture. It is strongly recommended
that batteries are replaced after 4 years of use. Batteries
must be disposed of as per recommendation made by
battery manufacturer.
&
Always use the recommended
replacement battery. As there is a risk of an
explosion if incorrect batteries are used.
¨
Switch On the mains supply to the panel and then
make the connection to the battery.
PANEL
P3
43V
FS6
1A P7
BAT1
-
+
Black
Red
- +
- +
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
PSU BOARD
Y1 Y2 G1
2 - 12V 12Ah battery