Appendix B - Message Action List

This appendix lists all the messages that are likely to be displayed at the control panel . There are some fault events that are not self
clearing and will require manual intervention.

Clearable fault events

The following faults are identified as clearable fault events.
¨
FLASH corrupt
¨
Invalid device configuration
¨
Too many errors
Can be cleared but will not reset the counters.
¨
Unrecoverable Tx fault
¨
Checksum error
FLASH Configuration data and FLASH in sensors
¨
NVM recovery failures or map mis-match
How to clear a clearable fault event
To clear the fault at the control panel press the Menu on/Off button -> [Test/Eng] -> [UserCode] -> enter your PIN (where
necessary) -> <etc> -> [Config] -> [Clear] -> [Fault] -> [Enter].

Latching fault events

The following faults are identified as latching events.
¨
Slave devices lost
¨
Loop allocation fault
¨
Invalid loop configuration
How to clear a latching fault event
To clear a latching fault it is necessary to re-allocate the loop circuit. To re-allocate a loop circuit refer to section headed How to
power a loop

Repairable fault events

¨
Loop (partial) short circuit.
¨
Ground break
How to clear a repairable fault event
To repair the fault at the control panel press the Menu on/Off button -> [Test/Eng] -> [UserCode] -> enter your PIN (where
necessary) -> [Loop] -> <etc> -> <etc> -> [Repair] -> [Loop] -> enter the loop number on which the fault resides -> [Enter].

Message Action list

The messages displayed at the control panel or loop repeat panels are given here in an alphanumerical order to provide guidance:
¨
on fault message
¨
likely meaning of the message
¨
along with suggestions on what initial actions may be taken to rectify the problem.
"
Only the messages that are applicable will appear on the display of the control panel or loop repeat panels.
¨
The term device was previously referred to as outstation.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Vigilon (EN & BS) Compact (VA) panels
97