Vigilon Repeat panel (EN)
2nd Fix Installation
Repeat panel 2nd fix part
À
Outer door assembly
Á
Inner door assembly
Â
Master Repeat Card
Ã
20 Way ribbon cable
Ä
40 Way ribbon cable
Å
Spares pack (includes battery leads)
Remove the protective temporary cover from the
a
backbox.
Fit the inner door Á to the repeat panel
b
enclosure, remembering to connect the earth
lead to door and then fit the outer moulded door
À.
Fit the Master Repeat Card into the backbox
c
and:
connect the transformer wires to terminal
block - P10.
connect battery wires Å supplied with the
spares to terminal block P9 (note the red wire
TERMINAL
CARD
MASTER
REPEAT
CARD
EARTH
LEAD TO
INNER
DOOR
RED
BLACK
EN54 Repeat inst. 4188-839.03_11-06
Quantity
1
1
1
1
1
1
ESD
BONDING
POINT
+VE 0V
FS1
2.5A
Auxiliary
D10
supply fuse
Red LED
(Loop communications)
D9
Green LED
(Power ON)
AC
P10
AC
P9
12V 7Ah battery
Data and installation instructions
connects to the + and black wire to the -
terminal respectively).
connect the ribbon cable from the terminal
card to connector - P14 on Master Repeat
Card.
connect the 40 way ribbon cable Ä from
Master Repeat Card connector P7 to Display
Key Card connector - P1.
connect the 20 way ribbon cable à from
Master Repeat Card connector P8 to Display
Key Card connector - P6.
Power-up the panel by connecting the mains
d
supply and then the battery supply, and note:
the green and amber LEDs on the Master
repeat card are lit
all lights on the panel facia are lit for a short
duration
a reset message appears on the display
the local buzzer sounds for a short duration
a battery disconnected message appears
the display shows:
MAIN PANEL OFF LINE
the System Fault LED is lit on the panel facia
MAINS
TERMINAL
Danger
BLOCK
D6
P14
Yellow LED
(Watchdog)
P21
P20
2.5A
Battery fuse
FS2
0V V
Transformer
BACK BOX
CAUTION
HAZARDOUS VOLTAGES REMAINS
AFTER OPERATION OF FUSE.
L
MAINS
FUSE
E
N
RESET
SW1
SWITCH
FILTER
P7
DKC
SELECTION
LINKS
P8