Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 143

For the fire alarm systems
Table of Contents

Advertisement

Installation instructions
new fibre Network Card (EN)
(VIG-NC-FO and VIG-NC-DOM-FO) for Vigilon Network
The fibre network card allows fast message passing to the
network. The card must be plugged into the backplane of the
panel or node in a dedicated slot. The fibre optic cables
connect directly to sockets on the card. There are two types of
fibre network cards for secure EN54 Vigilon network.
"
Where a fibre network card is plugged into a
control panel or a network node ensure their Local
Controller software is at Version 4.00 or later when
using VIG-NC-FO and version 4.16 or later when using
VIG-NC-DOM-FO.
¨
VIG-NC-FO Fibre Optic Network card
Using the Fibre Optic Network card VIG-NC-FO up to 31
Control panels and Network Nodes can be connected in a
secure loop. There can be up to 2Km Fibre Optic cable
distance between panel and node.
¨
VIG-NC-DOM-FO Fibre Optic Network card
(for Domain bridge)
Using the Fibre Optic Network card VIG-NC-DOM-FO up to
64 smaller networks can be connected to form a secure
domain. The Fibre Optic cable distance between nodes of the
smaller networks can be up to 2Km. The entire system can
have up to 200 panels/nodes.
new fibre Network Card (EN) 4188-790 issue 2_07/06
Specification
Overall size
144mm height x 100mm width
Node address
1 to 64
range
1 to 32
Baud
19.2K, 38.4K, 115.2K and
230.4K
Terminations /
ST connection is by means of the
Fibre Optics
ST sockets on the Network card.
Cable: Multi mode 62.5 / 125µm
Fibre 820nm wavelength
Weight
82g (approximate)
Operating
0°C to 45°C
temperature
Storage
-10°C to 55°C
temperature
Relative humidity
up to 90%
(non condenscing)
Connecting Panels and Nodes
End 1
Tx
Rx
P7
P4
Rx
Tx
P2
Control Panel or Network Node
Links P2 and P3 are booster links.
Normally the links are not fitted, however for
distance exceeding 750m the links must be fitted.
P2 settings are for End 1
P3 settings are for End 2
"
Ensure the patch leads are of the correct
length. The leads connect directly to the Fibre Network
Card and patch panel.
by Honeywell
(VIG-NC-DOM-FO)
(VIG-NC-FO)
End 2
Rx
Tx
P6
P5
Rx
Tx
P3
BACKPLANE
1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gent viglion compact voice alarmGent viglion compactGent viglion bs

Table of Contents