Generic Commissioning instructions

S-Cubed Mark II and S-Quad

Speech function
The new Mark II S-Cubed or S-Quad Speech sounder function is
provided by stored messages on a flash memory chip within the
assembly. The standard flash memory can hold up to 20 seconds
of audio and additionally it holds local complex attention tones,
such as the bell and DIN signals. Each signal output from an
S-Cubed or S-Quad Speech device consists of an attention tone
followed by a message. The attention tone can be a local
complex tone or a panel tone, such as the standard 'nee naw'
sound.
Programmable period
normally set at 10 seconds
can be configured up to 60 seconds
Attention tone
Standard
or Complex
tone
Programmable
Pre-speech silence
It is possible to reprogram factory set speech messages
Strobe function
In the event of a fire the appropriate S-Cubed or S-Quad device
in the system will output alarm signals according to the site
specific configuration and these can be either signal 1, 2 or 3
alarm:
¨
every 2s with signal 1
¨
every 1 second with signal 2
¨
every 1 second with signal 3
However the operation of the strobe with the signals 1, 2 and 3
can be changed at the commissioning stage. The strobe is
synchronised with S-Cubed and S-Quad strobes installed in the
same system.
"
The Disability Act 1995 recommends visual
alarms, like S-Cubed and S-Quad, are installed in
protected premises to warn occupants who are hard of
hearing.
126
Speech Message
Message n
Programmable
Post-speech silence
Sounder function
A new Mark II S-Cubed or S-Quad sounder can operate in turbo
mode if configured during commissioning to provide further 3dB
output. The sound outputs are based on the settings of the FABs
and SABs at the panel that gives changing levels over 2 seconds
duration in 8 time slots. The standard outputs are synchronised
with the 34000 sounders and other S-Cubed or S-Quad devices
installed in the same system.
The volume of the sound output can be individually set at the
device, note that the sound level should not be set lower than
65dBA at 1m for standards compliance. The system prevents
adjustment of volume down to zero. Another feature that can be
configured is the soft start that ramps the sound volume gradually
to the maximum level set at the device.
Turbo and Non Turbo Modes
The S-Cubed or S-Quad sounders can output in turbo and/or in
non turbo modes. When the panel commands a low or high tone
output at S-Cubed or S-Quad, if configured during
commissioning, the S-Cubed or S-Quad sounder will output turbo
and/or non turbo tones. The high and low FAB mappings are
used to change the tone output of the S-Cubed or S-Quad
sounder. The turbo mode outputs a waveform with a basic
frequency that is the same frequency as the resonant frequency
of the S-Cubed or S-Quad piezo. The non turbo mode outputs
modulated turbo waveform.
Turbo square wave
Turbo high tone
Turbo low tone - high output
Turbo low tone
Turbo rich high tone
Turbo rich low tone
Non-Turbo square wave
Non-Turbo high tone (Default)
Non-Turbo low tone - high output
Non-Turbo low tone (Default)
Non-Turbo rich high tone
Non-Turbo rich low tone
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.