Battery installation

VIG1-24 panel battery installation
Black
Red
VIG1-72 panel battery installation
It is recommended that the mains supply is switched
off
during battery installation.
Ensure the batteries are held in place while they
are being wired. Ensure the battery terminals
do not come into contact with the metal enclosure.
Place the two batteries in the lower shelf and lay them
horizontally with terminals facing outwards.
Fit the bolt, spade connector, washer and spring
washer to each battery terminal as shown above.
White.
Red
Fit the white link lead and then fit the red/black
fused lead to the battery terminals.
Raise the two batteries to an upright position
and push them back into the enclosure.
Black
Red
White.
Route the battery red/black lead through hole in shelf
and connect to the respective connectors on PCB,
located on the top right side of the enclosure.
Add two more batteries 'B' to the lower shelf and repeat
j
procedures
to
Where required, add four batteries to the upper shelf,
follow procedures
is that the red/black lead is directly connected to the
respective upper connectors on the PCB.
The panel will only power up after the mains supply
is switched
on
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Red
P20
Black
White
Red
Black
Black
n
.
j
o
to
. The only exception
.
Vigilon (EN & BS) Compact (VA) panels
It is recommended that the mains supply is switched
off
during battery installation.
Fit the bolt, spade connector, washer, spring washer to
each battery terminal.
Insert
right
hand battery into the back box.
Insert
left
hand battery into the back box.
Fit the link lead (white) to outer + and - spade connectors
on the two batteries.
Fit the battery lead
(red & black)
- spade connectors of the two batteries observing polarity.
Plug the battery connector into connector P20 located on
the bottom left of power supply PCB.
The panel will only power up after the mains supply
is switched on.
4 - 12V 21Ah batteries
Battery Box
Upper
shelf
Lower
shelf
A
B
8 - 12V 21Ah batteries
Battery Box
Upper
shelf
A
B
Lower
shelf
A
B
In-line fuse rated 10A QB ceramic 20mm x 5mm
assembly to inner + and
TH+
BT1+
BT2+
TH-
BT1-
BT2-
P6
P4 P3
P1
P2
TH1
TH+
BT1+
BT2+
TH-
BT1-
BT2-
P6
P4 P3
P1
P2
TH1
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gent viglion compact voice alarmGent viglion compactGent viglion bs

Table of Contents