Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 105

For the fire alarm systems
Table of Contents

Advertisement

Message
Interface Input
OC / restored
Interface input
operated /
released
number x on loop
y channel z
Interface input
SC / restored
number x on
loop y channel z
Interface output
SC or OC or
Restored number
x on loop y
channel y
Intermittent
Fault at card x
Invalid
configuration
Invalid
configuration at
card x
Invalid message
/ reply received
at card x
Invalid
message/reply at
card x
Invalid task
delay at card x
Invalid task
stage
IO line Enabled
/ Disabled at
Card x
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
associated with..
meaning..
Device
The end-of-line is not seen.
Device
Fixed extinguishant
interface unit input has
been triggered.
Device
The interface wiring is
short circuit. The value of
input is equal to or less
than 2V.
Device
The value of output is
equal to or less than 50%
for SC
or is TBA for OC.
Any Card
A fault has been picked up
by the MCC / MCB (main
control card/board).
Loop Processor Card
Loop recovered with
freeblocks ON.
Device
FLASH incorrectly
programmed
Loop Processor
Loop recovered with
Card
freeblocks ON.
Loop Processor
The message/reply received
Card
cannot be understood. The
communication can be
from a Repeat, Mimic,
Supervisor, Network or
Orator system.
Network Card
The message/reply has not
been understood from other
panels.
Any Card
Software error.
Any Card
Software error.
Loop Processor
The IO line is either
Card
enabled or disabled
automatically or manually.
Vigilon (EN & BS) Compact (VA) panels
..possible action
Check the wiring. The device
may have been removed, if so
refit the device to restore.
Follow the FE system reset
procedure to release the
input.
Check the interface wiring
and rectify to restore the
input.
Check the wiring and restore
the output circuit.
Replace the appropriate card
if the fault keeps reoccurring.
This is not allowed. Switch
OFF the freeblocks and
reallocate.
Replace the device
This is not allowed. Switch
OFF the freeblocks and
reallocate.
Ignore single occurrence and
record in log book.
Ignore for single occurrence
and record in log book.
Software errors will activate
a system reset.
Ignore single occurrence.
Record the event in log
book.
Software errors will activate
a system reset.
Ignore single occurrence.
Record the event in log
book.
If necessary, manually
enable/disable the IO line
using the [control] menu.
105