Generic Commissioning instructions

Exception (or Condition) Codes for S-Quads

Gen
Pos
type
No.
Description
1st
Optical
subfire
E
N
V
2nd
Heat subfire
I
O
R
N
M
E
3rd
N
Gas subfire
T
4th
5th
Optical/Gas
channel drift
or out of
range
6th
Heat channel
drift or out of
range
S
E
7th
Optical/Gas
N
channel
S
noisy (High
O
freq)
R
8th
Heat channel
noisy (High
frequency)
9th
device
D
firmware
E
V
I
C
10th
device
E
transmission
56
Exception codes
normal
sub fault band
band
0
1
None
Small signal
sensed
[Check
location, state
& type]
None
Small signal
sensed
[Check
location, state
& type]
-
Small signal
sensed
[Check
location, state
& type]
-
OK
OK
OK
Single HF
noise event
detected
OK
Single HF
noise event
detected
OK
Isolated fault
[Note/report]
OK
Low error rate
fault band
2
Subfire
[Check location,
state & type]
Subfire
[Check location,
state & type]
Subfire
[Check location,
state & type]
Close to
Out of limits
acceptable limit
[Clean/replace]
Out of limits
[Clean/replace]
Multiple HF
noise seen
(Check location
and report)
Multiple HF
noise seen
(check location
and report)
Repetitive fault
Total failure
[Note/report/
[Replace]
replace]
Medium error
High error rate
rate
[Replace]
[Report]