ES-50X Series
Intelligent Addressable
Fire Alarm Control Panels
General
The ES-50X, ES-50XC, ES-50XI, and ES-50XP are the latest intelli-
gent addressable fire alarm control panel (FACPs) from Fire•Lite
Alarms and are direct replacement for the MS-9050UD. The ES-50X
Series support up to 50 addressable devices in any combination of
detectors or modules. With an extensive list of powerful features, the
ES-50X Series programs just like Fire•Lite's other addressable panels,
yet fits into applications previously served only by conventional panels.
The ES-50X and ES-50XC feature a pre-installed IPOTS-COM, a dual
technology (POTS and IP) communicator. The POTS transmits system
status (alarms, troubles, AC loss, etc.) to a Central Station via the pub-
lic switched telephone network. The IP communicator's internet moni-
toring capability sends alarm signals over the Internet saving the
monthly cost of two dedicated business telephone lines. Although not
required, the secondary telephone line may be retained providing
backup communication over the public switched telephone line.
Optional cellular reporting is available using an HW-TG7F Series
Communicators or the CLSS Pathway.
The ES-50XP features an integrated CLSS Pathway Pro Communica-
tor, a dual-SIM (AT&T/ Verizon) 5G LTE-M Communicator with optional
IP connection. The CLSS Pathway Pro transmits system status
(alarms, troubles, AC loss, etc.) to the Central Station using LTE CAT-
M1 networks, serving as a bridge between the fire system and the
CLSS Cloud. The IP communicator's Internet monitoring capability
sends alarm signals over the Internet, meeting requirements for
backup communication. As an integrated communicator, the CLSS
Pathway Pro, typically, can transmit data faster than dial capture meth-
ods.
Remote and local programming of the control panel is possible using
the FS-Tools Upload/Download utility. Programming databases can be
uploaded/downloaded via the panel's USB port (and USB cable) or via
an ethernet connection using the IPOTS-COM communicator (ES-50X
and EX-50XC only). The USB port also allows for the download or
upload of the entire program, history file, walk-test data, current status
and system voltages by means of a USB flash drive.
The power supply and all electronics are contained on a circuit board
supported on a new quick install chassis and housed in a metal cabi-
net. Available accessories include local and remote upload/download
software, remote annunciators, and reverse polarity/city box transmit-
ter (4XTMF).
Features
• Listed to UL Standard 864, 10th edition
• Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Tele-
phone Service) Central Station Communicator (ES-50X and EX-
50XC only)
• Optional Cellular Central Station Communicators over AlarmNet®
(ES-50X and EX-50XC only)
• Integrated CLSS Pathway Pro Communicator; dual SIM AT&T/Veri-
zon networks with LTE-CAT-M1 5G technology (EX-50XP only)
• Cloud monitoring using Honeywell's Connected Life Safety Ser-
vices (CLSS) Cloud solutions software (EX-50XP only)
• Compatible with SWIFT® wireless devices
• Auto-programming (learn mode) reduces installation time. Reports
two devices set to the same address
• Two independently programmable, built-in, Class A or Class B NAC
circuits
• Selectable strobe synchronization for System Sensor, Wheelock,
and Gentex devices
• Notification Appliance Circuit End of Line resistor matching
Addressable Fire Alarm Control Panels
• Four programmable function keys for ease of maintenance
• Two programmable relays and one fixed trouble relay
• Built-in Programmer
• Integral 80-character LCD display with backlighting
• Real-time clock/calendar with automatic daylight savings control
• History file with 1,000 event capacity
• Addressable sounder base
• Multi-criteria detector (smoke, heat, CO) with programmable
response
• Control module delay timer
• Automatic detector sensitivity testing (NFPA 72 compliant)
• Automatic device type-code verification
• Point trouble identification
• Waterflow selection per module point
• Alarm verification selection per detector point
• Maintenance alert warns when smoke detector dust accumulation
is excessive
• One-person audible or silent walktest with walktest log & printout
• System alarm verification selection per detector point
• PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72
compliant)
• Up to 16 ANN-BUS annunciators- 8 per each ANN-Bus
• Remote Acknowledge, Alarm Silence, Reset and Drill via address-
able modules or remote annunciator
• Upload/Download of program and data via USB with optional
FS-Tools Programming Utility
SLC (DCL) COMMUNICATION LOOP
• Supports LiteSpeed™ and CLIP protocols
• SLC (DCL) operates up to 10,000 ft. (3,000 m) in LiteSpeed mode
with twisted, unshielded wire
• Single addressable SLC (DCL) loop which meets NFPA Class B
and Class A requirements
• 50 addressable device capacity (any combination of addressable
detectors and modules)
• Compatible with Fire•Lite's addressable devices (refer to the SLC
Wiring Manual)
DF-60953:D
DF-60953:D • 3/27/2023 — Page 1 of 4

Advertisement

loading

Summary of Contents for Honeywell FIRE-LITE ALARMS ES-50X Series

  • Page 1 FS-Tools Programming Utility zon networks with LTE-CAT-M1 5G technology (EX-50XP only) SLC (DCL) COMMUNICATION LOOP • Cloud monitoring using Honeywell’s Connected Life Safety Ser- vices (CLSS) Cloud solutions software (EX-50XP only) • Supports LiteSpeed™ and CLIP protocols • SLC (DCL) operates up to 10,000 ft. (3,000 m) in LiteSpeed mode •...
  • Page 2 NOTIFICATION APPLIANCE CIRCUITS (NACS) HW-TG7FE-A/HW-TG7FE-V: CLSS-Enabled 5G/LTE-M Dual Path Commercial Fire Alarm Communicators for AT&T and Verizon • Two independently programmable output circuits. Circuits can be HW-TG7FP-A/HW-TG7FP-A: CLSS-Enabled 5G/LTE-M Sole Path configured for Class A or Class B wiring. Commercial Fire Alarm Communicators for AT&T and Verizon –...
  • Page 3 H365(A)-IV: Low-profile 135°F fixed thermal sensor. Ivory. LiteSpeed BG-12LX: Addressable manual pull station with interface module and CLIP mode. mounted inside. I300(A): This module isolates the SLC (DCL) loop from short circuit H365R(A): Low-profile, intelligent, rate-of-rise thermal sensor. Lite- conditions (required for Class A or Class X operation). Speed only.
  • Page 4 L.P.Verizon® is a registered trademark of Verizon Trademark Services LLC. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. ©2023 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes.