Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 101

For the fire alarm systems
Table of Contents

Advertisement

Message
Clock changed /
Clock not set up
CO sensor faulty
CO sensor near
end of life
CO sensor
restored
Command build
activated/deacti
vated
Command build
enabled /
disabled
Comms
Enabled/Disabled
at card x
Comms Supply
Fault
Comms supply
Restored
Communications
started/stopped
at Card x
Control passed
at Card x
Corrupted NVM
memory at card x
DC Power fail
restored
DC too high / DC
too low
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
associated with..
meaning..
MCC / MCB (main
Time and date has been
control card/board)
altered or no time has been
entered.
Device
There is a fault with the CO
sensor on S-Quad.
Device
The CO cell is nearing the
end manufacturer
recommended life
expectancy (S-Quad).
Device
The CO sensor fault has
been restored (S-Quad)
MCC / MCB (main
Command build has been
control card/board)
switched ON (activated) or
OFF (deactivated).
MCC /MCB (main
This is an automatic or
control card/board)
manually controlled action.
MCC / MCB (main
Card communications have
control card/board)
been enabled or disabled.
Control panel has been
Network Card
isolated from the network.
Network node
The communications power
supply has failed.
Network node
The communications power
supply has been restored.
MCC / MCB (main
Communication to a
control card/board)
particular panel or to
external equipment linked
to the panel (eg Laptop for
com. tool) has started /
stopped.
Network
-
Any Card
Checksum failure on
configuration at midnight.
Power supply
The ADC of output 27V
regulator
Normal=146(28.5V).
Power supply
The DC supply is:
Too high if greater than
164 (32V)
Too low if less than 102
(20V)
Vigilon (EN & BS) Compact (VA) panels
..possible action
If necessary, set the clock
using the set up menu.
Replace device
Replace the device
If necessary switch ON/OFF
the command build using the
[control] menu.
If necessary, manually
enable/disable the command
build using the [control]
menu.
If necessary, manually
enable/disable the Comms
using the [control] menu
Replace the power supply
unit.
-
Check the wiring.
-
Recover data and record in
log book. If it reoccurs then
replace the card.
-
Check the mains supply.
101