Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 118

For the fire alarm systems
Table of Contents

Advertisement

Generic Commissioning instructions
Integral sounder operation
¨
Integral sounder sector operation (also called flag set sector) can be configured using the menu commands
[SetUp]-> [Sector] -> [Sounder] -> [On].
INTEGRAL SOUNDER SECTOR FUNCTIONS
SECTOR X
OHS
FIRE
Setup
H
MCP
INTERFACE
A sector configured for integral sounder operation will in the event of a fire at an optical heat sensor sounder (OHS) device will
operate ONLY the local sounder (of the OHS).
Default fire plan
¨
The fire plan on power up is known as 'one out all out'. This is when sector 1 is assigned with all devices of the
system. A fire will activate evacuate (signal 2) on all interface outputs and alarm sounders.
¨
Fixed extinguishant inputs / outputs are automatically assigned to sector 29. Note the Fixed extinguishing interface
unit is no longer a part of the product range.
To assign a default fire plan
¨
To manually configure the default fire plan using the set up menu:
Assign all device and IO lines to sector 1
and then action all sectors (except sectors 29-32) on all sectors to signal 2.
To remove the default fire plan.
¨
If the system is not intended to operate with the default 'Fire Plan', then do exactly the same as making the default
fire plan, but this time replace the [Assign] with [Remove]. Also remove IO lines.
¨
monitored line is a circuit of MCPs off a sensor, not allowed for the UK , this must be removed
¨
all sensors, call points, sounders and interface lines are now completely separate from each other
¨
also [Deaction] all sectors on all sectors. This will remove any configured sector actions
¨
a site specific 'Fire Plan' can now be set up by assigning devices within common initiation areas to sectors and then
actioning them together to form the required 'Fire Plan'.
Fail safe fire plan
¨
It is advisable to build a fail safe mechanism when sectoring. If for any reason certain sector assignment has been
lost due to system power down and subsequent NVM recovery conflicts on system power up, the sounders will still
operate in the event of a fire.
¨
the fail safe mechanism will involve leaving Sector 1 on each loop free from any device assignment, as any devices
that lose their sector assignment will default to Sector 1.
¨
the following action will give an evacuate tone to any alarm sounders that have defaulted to Sector 1:
Action all sectors (except sectors 29-32) on sector 1
to signal 2
Action sector 1 on all sectors (except Sector 1 and Sectors 29-32) to signal 2
Site specific fire plan
¨
A site specific fire plan can be created by configuring sectors.
118
SECTOR X
OHS
INTEGRAL
FLAG SET
ON
SOUNDER - ON
INTEGRAL
SOUNDER
FLAG
OFF
SET OFF
(DEFAULT)
DEFAULT
1) The
2) The
NOTE: OTHER OPTICAL HEAT SOUNDERS
IN AN `INTEGRAL SOUNDER SECTOR'
OPERATE IN A SIMILAR MANNER
SECTOR X
OPERATION
ONLY LOCAL
ALARM SOUNDS
FIRE
ACTION
H
ACTION
MCP
INTERFACE
ACTION
sector x
will operate normally.
sector x
will operate normally when
actioned by another sector.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
COMMAND
BUILD
DELAY
BLOCK
SECTOR
This action is only applicable
if the
fire
was from a
non
OHS sensor