Exception Codes For Heat Sensor - Honeywell Gent Viglion EN54 Generic Commissioning Instructions

For the fire alarm systems
Table of Contents

Advertisement

Generic Commissioning instructions

Exception codes for Heat sensor

Gen
Pos
type
No.
Description
1st
Subfire
background
E
N
V
2nd
Subfire
I
foreground
O
R
N
M
3rd
E
N
T
4th
5th
Drift out of
range high
6th
Heat channel
S
drift or out of
E
range
N
S
O
7th
Noisy (High
R
frequency)
8th
D
9th
device
E
firmware
V
I
C
E
10th
device
transmission
54
Exception codes
normal
sub fault band
band
0
1
None
Small signal
sensed [Check
location, state
& type]
None
Small signal
sensed [Check
location, state
& type]
OK
OK
OK
Single HF
noise event
detected
OK
Isolated fault
[Note/report]
OK
Low error rate
fault band
2
3
Subfire
[Check location,
state & type]
Subfire
[Check location,
state & type]
Above upper
limit
T
>250
9
[Replace]
Below lower
limit
T
11<20
[Replace]
Multiple HF
noise seen
Repetitive Fault
Total Failure
[Note/report/
[Replace]
replace]
Medium error
High error
rate
rate
[Report]
[Replace]
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.