Installation Instructions - Honeywell Gent Viglion EN54 Generic Commissioning Instructions

For the fire alarm systems
Table of Contents

Advertisement

Installation instructions

Copper Network Card (BS)
(VIG/34K-NC-V3+) for BS5839 Vigilon or 34K Network
This copper network card is used to allow messages of status
and control data to pass between control panels and network
(or terminal) nodes in a networked fire system. The card must
be plugged into the backplane of each panel and node in a
dedicated slot. When it is plugged into the slot P8 on the
backplane the external cables must be connected to terminal
block P10, which is also located on the backplane.
The dual-in-line switches on the card are set to program the
address number and baud rate.
Connecting the Panels and Nodes
From
previous
panel
or node
No
connection
1
0V -ve +ve 0V I -ve +ve I
Connections for
Network card in
Socket P8 (Card 6)
Copper Network Card (BS) 4188-789 issue 2_12/05
The 0V connection
is as shown.
Cable screen
P10
2
3
4
5
6
7
8
BACKPLANE
Control Panel
or Network Node
This network card can be installed in:
Vigilon or 34K Fire Panels
VIG1-V3+
VIG1-NET-V3+
VIG2-V3+
VIG2-NET-V3+
VIG3-V3+
VIG3-NET-V3+
VIG4-V3+
VIG4-NET -V3+
Vigilon or 34K Network (or Terminal) Node
VIG-NODE-V3+ or 34K-NODE-V3+
Specification
Overall size
128mm height x 100mm width
Node address range
1 to 31
Baud
2400, 9600, 19.2K and 38.4K
Operating voltage
±5V (RS485)
Terminations
Terminal block P10 assuming
Network card is installed in
backplane slot P8
Cable
Belden 9729 (example)
Weight
72g (approximate)
Operating
0°C to 45°C
temperature
Storage temperature
-10°C to 55°C
Relative humidity
up to 90%
(non condenscing)
Using the Copper Network card a maximum of up to 31 Control
panels and Network (Terminal) nodes can be connected in a
secure network loop, with up to 1.2Km cable distance between
panels/nodes dependent on cable type.
No
connection
1
2
3
4
5
6
0V -ve +ve 0V I -ve +ve I
Connections for
Network card in
Socket P8 (Card 6)
BACKPLANE
Control Panel
Network Node
by Honeywell
or 34K1-V3+
To Next
panel
or node
P10
7