Generic Commissioning instructions
Message
Delay block
setup
Delay blocks
Cleared
Detection Zone
Disabled/Enabled
at card x
Detector on
interface unit
number x on
loop y channel z
Device Address
Changed from x
number y on
loop z
Device battery
fault /restored
Device Battery
OC number x on
loop y
Device Enabled /
Disabled at
Card x
Device Fault
number x on
loop y
Device Gain set
to x number y on
loop z
Device Mains too
high / low
number x loop y
Device power
Fault / Restored
number x on
loop y
102
associated with..
meaning..
MCC / MCB (main
A Delay Block has been
control card/board)
configured.
MCC / MCB (main
-
control card/board)
Loop Processor
The detection zone has
Card
been enabled or disabled
automatically or manually.
Device
Mains powered interface
input has been triggered by
conventional detector.
Value of the input is equal
to or less than 10V.
Loop Processor
Device SAFE address has
Card
changed.
Device
The battery has failed the
load test.
For a mains powered
interface the value is equal
to or less than normal - 2V.
Device
Failure of fuse or battery
wiring is OC on products
like mains powered
interface unit.
Normal value = 27.4V
Value is equal to or less
than 16V (OC) / greater
than 17V (Restored).
Loop Processor
Device has been enabled or
Card
disabled manually or
automatically.
Audio Control Unit
Fault input has been
asserted.
Beam and Flame
Confirmation of a change
devices
in gain setting.
Devices like: Mimic
Failure of device mains
/ Repeat / Mains
supply.
powered interface
The value of rectified DC
unit
is too high / low i.e in the
region of 30V / 17V.
Device
The failure of internal
power supply rail.
..possible action
-
-
If necessary, manually
enable/disable the Detection
zone using the [control]
menu.
-
If necessary rectify the device
SAFE address.
Check and replace the battery
if necessary.
Check and replace if
necessary to restore.
If necessary manually enable
or disable the device.
Check remote equipment
wired to the fault input.
-
Check the power supply and
replace it if necessary
Replace the device.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.