Electrical Data, 525-690 - Danfoss VLT AutomationDrive FC 300 Design Manual

90–1200 kw
Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

Selection
4.2 Electrical Data, 525–690 V
FC 302
High/Normal load*
Typical shaft output at 550 V [kW]
Typical shaft output at 575 V [hp]
Typical shaft output at 690 V [kW]
Enclosure IP21
Enclosure IP54
Enclosure IP20
Output current
Continuous (at 550 V) [A]
Intermittent (60 s overload) (at 550 V)
[A]
Continuous (at 575/690 V) [A]
Intermittent (60 s overload)
(at 575/690 V) [kVA]
Continuous kVA (at 550 V) [kVA]
Continuous kVA (at 575 V) [kVA]
Continuous kVA (at 690 V) [kVA]
Maximum input current
Continuous (at 550 V) [A]
Continuous (at 575 V) [A]
Continuous (at 690 V)
Max. cable size: line power, motor,
2
brake and load share mm
(AWG)
Max. external electrical fuses [A]
Estimated power loss at 575 V [W]
Estimated power loss at 690 V [W]
Weight, enclosure IP21, IP54 kg (lbs)
Weight, enclosure IP20 kg (lbs)
4)
Efficiency
Output frequency
Heatsink overtemperature trip
Control card ambient trip
*High overload=150% current for 60 s, Normal overload=110% current for 60 s.
Table 4.6 Technical Specifications, D-frame, 525–690 V Line Power Supply 3x525–690 V AC
1) American Wire Gauge.
2) For fuse ratings, see chapter 7.2.1 Fuses.
3) Typical power loss is at normal conditions and expected to be within
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the adjustable frequency drive.
If the switching frequency is raised from nominal, the power losses rise significantly. LCP and typical control card power consumptions are
included. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B
each add only 4 W.
4) Measured using 16.5 ft. [5 m] shielded motor cables at rated load and rated frequency.
MG34S222
Design Guide
N55K
HO
NO
HO
45
55
55
60
75
75
55
75
75
D1h
D1h
D3h
76
90
90
122
99
135
73
86
86
117
95
129
72
86
86
73
86
86
87
103
103
77
89
89
74
85
85
77
87
87
1)
160
2)
3) 4)
1098
1162
1162
3) 4)
1057
1204
1205
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
N75K
N90K
NO
HO
NO
75
75
90
100
100
125
90
90
110
D1h
D1h
D1h
D1h
D3h
D3h
113
113
137
124
170
151
108
108
131
119
162
144
108
108
131
108
108
130
129
129
157
110
110
130
106
106
124
109
109
128
2x95 (2x3/0)
315
315
1428
1430
1740
1477
1480
1798
62 (135)
125 (275)
0.98
0–590 Hz
230 °F [110 °C]
167 °F [75 °C]
± 15% (tolerance relates to variety in voltage and cable conditions.) These
N110
N132
HO
NO
HO
NO
90
110
110
132
125
150
150
200
110
132
132
160
D1h
D1h
D1h
D1h
D3h
D3h
137
162
162
201
206
178
243
221
131
155
155
192
197
171
233
211
131
154
154
191
130
154
154
191
157
185
185
229
130
158
158
198
124
151
151
189
128
155
155
197
315
315
1742
2101
2080
2649
1800
2167
2159
2740
4
4
69