Danfoss VLT AutomationDrive FC 300 Design Manual page 223

90–1200 kw
Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

Electrical Installation
Figure 7.34 Different Parallel Connections of Motors
A
Installations with cables connected in a common joint as shown in A and B are only recommended for short cable lengths.
B
Be aware of the maximum motor cable length specified in chapter 4.3 General Specifications.
C
The total motor cable length specified in chapter 4.3 General Specifications is valid as long as the parallel cables are kept short less
than 10 m each. (Example 1).
D
Consider voltage drop across the motor cables. (Example 1).
E
Consider voltage drop across the motor cables. (Example 2).
F
The total motor cable length specified in chapter 4.3 General Specifications is valid as long as the parallel cables are kept less than
10 m each. (Example 2).
Table 7.65 Legend to Figure 7.34