Selection
FC 302
High/Normal load*
Typical shaft output at 400 V [kW]
Typical shaft output at 460 V [HP]
Typical shaft output at 500 V [kW]
Enclosure IP21
Enclosure IP54
Enclosure IP00
Output current
Continuous (at 400 V) [A]
Intermittent (60 s overload)
(at 400 V) [A]
Continuous (at 460/500 V) [A]
Intermittent (60 s overload)
(at 460/500 V) [A]
Continuous kVA (at 400 V) [kVA]
Continuous kVA (at 460 V) [kVA]
Continuous kVA (at 500 V) [kVA]
Maximum input current
Continuous (at 400 V) [A]
Continuous (at 460/500 V) [A]
Max. cable size, line power, motor and
2
1)2)
load share [mm
(AWG)]
Max. cable size, brake [mm
2
(AWG)
3)
Max. external electrical fuses [A]
Estimated power loss at 400 V [W]
Estimated power loss at 460 V [W]
Weight, enclosure IP21, IP54 [kg]
Weight, enclosure IP00 [kg]
5)
Efficiency
Output frequency
Heatsink overtemp. trip
Control card ambient trip
* High overload=160% torque during 60 s, Normal overload=110% torque during 60 s.
Table 4.2 Technical Specifications, E-frame 380–500 V Line Power Supply 3x380–500 V AC
1) American Wire Gauge.
2) Wiring terminals on N132, N160, and P315 adjustable frequency drives cannot receive cables one size larger.
3) For fuse ratings, see chapter 7.2.1 Fuses.
4) Typical power loss is at normal conditions and expected to be within
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the adjustable frequency drive.
If the switching frequency is raised from nominal, the power losses rise significantly. LCP and typical control card power consumptions are
included. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B
each add only 4 W.
5) Measured using 16.5 ft. [5 m] shielded motor cables at rated load and rated frequency.
MG34S222
Design Guide
P315
HO
NO
315
355
450
500
355
400
E1
E1
E2
600
658
900
724
540
590
810
649
416
456
430
470
468
511
590
647
531
580
4x240 (4x500 mcm)
1)
2x185 (2x350 mcm)
900
4) 5)
6794
7532
4) 5)
6118
6724
270
234
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
P355
HO
NO
355
400
500
600
400
500
E1
E1
E2
658
745
987
820
590
678
885
746
456
516
470
540
511
587
647
733
580
667
4x240 (4x500 mcm)
2x185 (2x350 mcm)
900
7498
8677
6672
7819
272
236
0.98
0–590 Hz
230 °F [110 °C]
185 °F [85 °C]
± 15% (tolerance relates to variety in voltage and cable conditions.) These
P400
HO
NO
400
450
550
600
500
530
E1
E1
E2
695
800
1043
880
678
730
1017
803
482
554
540
582
587
632
684
787
667
718
4x240 (4x500 mcm)
2x185 (2x350 mcm)
900
7976
9473
7814
8527
313
277
65
4
4
Need help?
Do you have a question about the VLT AutomationDrive FC 300 and is the answer not in the manual?
Questions and answers