Motor Thermistor; Relay Set-Up With Smart Logic Control - Danfoss VLT AutomationDrive FC 300 Design Manual

90–1200 kw
Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

Application Examples

8.8 Motor Thermistor

CAUTION
Thermistors must use reinforced or double insulation to
meet PELV insulation requirements.
VLT
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 8.12 Motor Thermistor
MG34S222
Design Guide
Parameters
Function
Setting
1-90 Motor
[2]
Thermal
Thermistor
Protection
trip
1-93 Thermistor
[1] analog
Source
input 53
*=Default Value
Notes/Comments:
If only a warning is desired,
1-90 Motor Thermal Protection
should be set to [1] Thermistor
warning.
Danfoss A/S © Rev. 2014-02-10 All rights reserved.

8.9 Relay Set-up with Smart Logic Control

FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
06
Parameters
Function
Setting
4-30 Motor
[1]
Feedback Loss
Warning
Function
4-31 Motor
100 RPM
Feedback Speed
Error
4-32 Motor
5 s
Feedback Loss
Timeout
7-00 Speed PID
[2] MCB
Feedback Source
102
17-11 Resolution
1024*
(PPR)
13-00 SL
[1] On
Controller Mode
13-01 Start Event [19]
Warning
13-02 Stop Event [44]
Reset
key
13-10 Comparator
[21]
Operand
Warning
no.
13-11 Comparator
[1]*
Operator
13-12 Comparator
90
Value
13-51 SL
[22]
Controller Event
Compar
ator 0
13-52 SL
[32] Set
Controller Action
digital
out A
low
5-40 Function
[80] SL
Relay
digital
output
A
*=Default Value
245
8
8