Electrical Installation
Frame size
F8-F13
Table 7.55 Control Transformer Fuse
Frame size
F8-F13
Table 7.56 NAMUR Fuse
Frame size
F8-F13
Table 7.57 Safety Relay Coil Fuse with Pilz Relay
Frame
Power & Voltage
size
P450 380–500 V & P630-P710
F3
525–690 V
P500-P630 380–500 V & P800
F3
525–690 V
P710 380–500 V & P900-P1M2
F4
525–690 V
F4
P800 380–500 V
Table 7.58 F-frame Circuit Breakers
7.3 Disconnectors and Contactors
7.3.1 Line Power Disconnects - Frame Sizes E and F
Frame size
380–500 V
D5h/D6h
D7h/D8h
E1/E2
E1/E2
F3
F3
F4
525–690 V
D5h/D6h
D7h/D8h
E1/E2
F3
F3
F4
Table 7.59 Line Power Disconnects, 6-Pulse Adjustable Frequency Drives
MG34S222
Design Guide
Bussmann PN
LPJ-6 SP or SPI
Bussmann PN
GMC-800 MA
Bussmann PN
LP-CC-6
Type
Merlin Gerin
NPJF36120U31AABSCYP
Merlin Gerin
NRJF36200U31AABSCYP
Merlin Gerin
NRJF36200U31AABSCYP
Merlin Gerin
NRJF36250U31AABSCYP
Power
N55K–N132
N160–N315
P250
P315–P400
P450
P500–P630
P710–P800
N90K–N132
N160–N250
P355–P560
P630–P710
P800
P900–P1M2
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
Rating
6 A, 600 V
Any listed Class J Dual Element,
Rating
800 mA, 250 V
Rating
6 A, 600 V
Any listed Class CC, 6 A
Default breaker settings
Trip level [A]
1200
2000
2000
2500
Type
ABB OT400U03
ABB OT600U03
ABB OETL-NF600A
ABB OETL-NF800A
Merlin Gerin NPJF36000S12AAYP
Merlin Gerin NRKF36000S20AAYP
Merlin Gerin NRKF36000S20AAYP
ABB OT400U03
ABB OT600U03
ABB OETL-NF600A
Merlin Gerin NPJF36000S12AAYP
Merlin Gerin NRKF36000S20AAYP
Merlin Gerin NRKF36000S20AAYP
Alternative fuses
Time Delay, 6 A
Alternative fuses
Time [s]
0.5
0.5
0.5
0.5
217
7
7
Need help?
Do you have a question about the VLT AutomationDrive FC 300 and is the answer not in the manual?