Electrical Installation
2.5–4.0 A Fuse
4.0–6.3 A Fuse
6.3–10 A Fuse
10–16 A Fuse
7
7
Table 7.42 Manual Motor Controller Fuses
Frame Size
F
Table 7.43 30 A Fuse Protected Terminal Fuse
Frame size
F
Table 7.44 Control Transformer Fuse
Table 7.45 NAMUR Fuse
Frame size
Table 7.46 Safety Relay Coil Fuse with PILZ Relay
214
Size/Type
P450-P800, 380–500 V
P630-P1M2, 525–690 V
P450-P800, 380–500 V
P630-P1M2, 525–690 V
P450-P800, 380–500 V
P630-P1M2, 525–690 V
P450-P800, 380–500 V
P630-P1M2, 525–690 V
Bussmann PN
LPJ-30 SP or SPI
Bussmann PN
LPJ-6 SP or SPI
Frame Size
F
Bussmann PN
F
LP-CC-6
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
Design Guide
Bussmann PN
LPJ-6 SP or SPI
LPJ-10 SP or SPI
LPJ-10 SP or SPI
LPJ-15 SP or SPI
LPJ-15 SP or SPI
LPJ-20 SP or SPI
LPJ-25 SP or SPI
LPJ-20 SP or SPI
Rating
30 A, 600 V
Rating
6 A, 600 V
Bussmann PN
GMC-800 MA
6 A, 600 V
Rating
6 A, 600 V
Any listed Class J Dual
Element, Time Delay, 6 A
10 A, 600 V
Any listed Class J Dual
Element, Time Delay, 10 A
10 A, 600 V
Any listed Class J Dual
Element, Time Delay, 10 A
15 A, 600 V
Any listed Class J Dual
Element, Time Delay, 15 A
15 A, 600 V
Any listed Class J Dual
Element, Time Delay, 15 A
20 A, 600 V
Any listed Class J Dual
Element, Time Delay, 20 A
25 A, 600 V
Any listed Class J Dual
Element, Time Delay, 25 A
20 A, 600 V
Any listed Class J Dual
Element, Time Delay, 20 A
Alternative fuses
Any listed Class J Dual Element, Time Delay, 30 A
Alternative fuses
Any listed Class J Dual Element, Time Delay, 6 A
Rating
800 mA, 250 V
Rating
Alternative fuses
Any listed Class CC, 6 A
Alternative fuses
MG34S222