Tables, data records
3.5 Modbus data tables
3.5.2.13

Basic device parameter 1

Read access to the device parameters is possible from the register memory area with
function codes 03 and 04.
Individual parameter data (marked with the motor symbol in the "Info" column) can be written
via Modbus RTU via the register memory area with function codes 06 and 16. This function
can be used to adjust settings such as the rated motor current during operation of the motor.
Max. data record length per access: 46 registers.
The "SIMOCODE ES (TIA Portal)" software is nonetheless required for full parameterization
of the SIMOCODE pro V Modbus devices (see also Chapter "Commissioning with
Modbus RTU" in the SIMOCODE pro – System Manual
(https://support.industry.siemens.com/cs/ww/en/view/109743957)).
Table 3- 84
Basic device parameter 1
Input/holding register
Address
high/low Bit
0x4180
0x4182
0x4186
high
0
1
2
3
4
5
6
7
low
0
1
2
3
4
5
6
7
294
Designation
Type
Coordination
Byte
[4]
Device
Byte
configuration
[8]
No configuration
Bit
fault due to OP
Startup
Bit
parameter block
active
TEST/RESET
Bit
buttons blocked
Bus and
Bit
PLC/PCS - Reset
Reserved
Bit
Reserved
Bit
Reserved
Bit
Reserved
Bit
Diagnostics for
Bit
process events
Diagnostics for
Bit
process warnings
Diagnostics for
Bit
process faults
Diagnostics for
Bit
device faults
Reserved
Bit
Reserved
Bit
Bus monitoring
Bit
PLC/PCS
Bit
monitoring
Range
Unit
Default Comments
0, 1
0
0, 1
0
0, 1
0
0, 1
0
0
0
0
0
0, 1
0
0, 1
1
0, 1
1
0, 1
1
0
0
0, 1
1
0, 1
1
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Info
0 = Manual
1 = Auto