Communication
2.2 PROFINET communication
Example of the diagnostics data records
The following example shows the content of the data record 0xC010 with the pending fault
"execution of ON command":
Table 2- 27
BlockType
BlockLength
BlockVersion
API
SlotNumber
SubslotNumber
ChannelNumber
ChannelProperties
USI (User Structure Identifier)
ChannelNumber
ChannelProperties
ChannelErrorType
76
Content of data record 0xC010 for the pending fault "execution ON command"
0x0010: Diagnostics data record
0x0016: Block length 22 bytes
0x0101: always 0x0101 in the case of SIMOCODE
0x00000000: always 0 in the case of SIMOCODE
0x0001: Slot 1 - I/O address
0x0001: Sub-slot 1
0x8000: Submodule
0x0800: Pending diagnostics
0x8000: Channel diagnostics
0x0000: always 0 in the case of SIMOCODE
0x6804: Pending diagnostics
0x1000: Execution ON command